Very long control cables and analogue signals may in rare
cases and depending on installation result in 50/60 Hz
earth loops due to noise from mains supply cables.
If this occurs, it may be necessary to break the screen or
insert a 100 nF capacitor between screen and chassis.
The digital and analog inputs and outputs must be
connected separately to the frequency converter common
inputs (terminal 20, 55, 39) to avoid earth currents from
both groups to affect other groups. For example, switching
on the digital input may disturb the analog input signal.
Input polarity of control terminals
PNP (Source)
Digital input wiring
12
13
18
19
27
Illustration 3.81
NPN (Sink)
Digital input wiring
12
13
18
19
27
Illustration 3.82
VLT AQUA Drive FC 202 Operation Instructions
29
32
33
20
37
29
32
33
20
37
MG20P402 - Rev. 2013-12-16
NOTICE
Control cables must be screened/armoured.
Illustration 3.83
Remember to connect the shields in a proper way to
ensure optimum electrical immunity.

3.6.24 Switches S201, S202, and S801

Switches S201 (A53) and S202 (A54) are used to select a
current (0-20 mA) or a voltage (-10 to +10 V) configuration
of the analog input terminals 53 and 54.
Switch S801 (BUS TER.) can be used to enable termination
on the RS-485 port (terminals 68 and 69).
See Illustration 3.79.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF