APPENDIXES
Appendix 2 How to Use the QJ71DN91 in System of MELSEC iQ-R Series
A
RQ extension base unit
Refresh read time
265.14μs
App - 2
By using RQ extension base unit, the QJ71DN91 can be used in the system of
MELSEC iQ-R series.
For details, refer to the MELSEC iQ-R Module Configuration Manual.
(1) Precautions
(a)
The mode switch can be set in range of 0 to 8.
(b)
If the mode switch is set to the range other than 0 to 8 or the node number
switch is set to the range other than 0 to 63, an error (2241H: Parameter
error (module)) occurs in the CPU module of MELSEC iQ-R series.
(c)
Set parameters in a sequence program because the following cannot be
set in GX Works3.
Master function parameters (Refer to Section 7.3.2 (1) (2).)
Slave function parameters (Refer to Section 8.2.2 (1).)
Save Parameters to Flash ROM (Refer to Section 7.3.2 (3), 8.2.2 (2).)
(2) Refresh processing time
When the QJ71DN91 is used for MELSEC iQ-R series, the refresh processing
time for when "Target" is a refresh data register (RD) is as follows.
Refresh write time
155.06μs
For the refresh processing time for when "Target" is a specified device, refer to the
MELSEC iQ-R CPU Module User's Manual (Application).
Q extension base unit
Refresh read time
599.57μs
MELSEC-Q
Refresh write time
327.80μs