10 TROUBLESHOOTING
Error
Detected
code
in:
(Dec.)
The requested service cannot be executed in the
16
Slave node
current device status.
17
QJ71DN91
Slave node did not respond.
Sufficient data was not provided to execute the
19
Slave node
specified operation.
20
Slave node
The specified attribute is not supported.
21
Slave node
The service provided excessive data.
The specified object does not exist in the slave
22
Slave node
node.
50
QJ71DN91
The response data format is invalid.
55
QJ71DN91
The specified slave node No. is other than 0 to 63.
57
QJ71DN91
The divided data were received in incorrect order.
The data length set in the buffer memory is 241 or
257
QJ71DN91
more.
An invalid value was set as a command No. in the
258
QJ71DN91
Message Communication Command area of the
buffer memory.
300
QJ71DN91
The own node is set offline.
301
QJ71DN91
An error occurred during data queuing.
302
QJ71DN91
A timeout occurred while waiting for a response.
303
QJ71DN91
An invalid response was obtained.
The specified node No. is currently set for a
304
QJ71DN91
reserved node.
305
QJ71DN91
The message was sent to the own node.
10 - 14
Description
Action
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
• Referring to the slave node manual, check the
condition under which the slave node notifies this
error, and take an appropriate action.
• Check the entire network and slave node states for
any fault such as slave node failure, or disconnection
of a terminating resistor.
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
• In the case of set attribute, verify that the specified
data is sufficient and the data length is correct.
• Referring to the slave node manual, check the
condition under which the slave node notifies this
error, and take an appropriate action.
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
• Referring to the slave node manual, check the
condition under which the slave node notifies this
error, and take an appropriate action.
• Reduce the data returned from the slave node to 240
bytes or less.
• Check whether or not the specified MAC ID, class ID,
instance ID and attribute ID are correct.
• Referring to the slave node manual, check the
condition under which the slave node notifies this
error, and take an appropriate action.
• Check the entire network and slave node states for
any fault such as disconnection of a terminating
resistor.
• Specify a node No. in the range of 0 to 63.
• Check the entire network and slave node states for
any fault such as disconnection of a terminating
resistor.
• Set the data length to 240 bytes or less.
• Set 0001
, 0101
, 0102
, 0201
H
H
H
command No.
• Set Y11 to on to set the own node online.
• Perform a hardware test to check for hardware failure.
• Check the entire network and slave node states for
any fault such as disconnection of a terminating
resistor.
• Check the entire network and slave node states for
any fault such as disconnection of a terminating
resistor.
• Set a node No. that is not being used for a reserved
node.
• Send messages to address any other than the own
node.
MELSEC-Q
, or FE**
as a
H
H
10 - 14

Advertisement

Table of Contents
loading

Table of Contents