3 SPECIFICATIONS
3 - 30
(5) Failed Node Detection Setting (address: 01CC
463)
Whether or not to detect a failed node is set in this area.
The setting determines whether or not the off status in Node Communication
Status (address: 01BC
• When the corresponding bit is on: Slave Down Signal (X04) is not set to on even
• When the corresponding bit is off: Slave Down Signal (X04) is set to on if the
Table 3.23 Node No. corresponding to each bit in Failed Node Detection Setting
Buffer memory address
(Hex.)
01CC
H
01CD
H
01CE
H
01CF
H
POINT
For a node that is set as a reserved node with a master function parameter, turn on
the corresponding bit of Failed Node Detection Setting. If it remains off, it is
recognized as a failed node even if it is just a reserved node.
to 01BF
) is reflected to Slave Down Signal (X04).
H
H
if the slave node went down.
slave node went down.
Node No. corresponding to each bit
Bit 15
Bit 14
Node 15
Node 14
Node 31
Node 30
Node 47
Node 46
Node 63
Node 62
MELSEC-Q
to 01CF
/460 to
H
H
Bit 1
Bit 0
Node 1
Node 0
Node 17
Node 16
Node 33
Node 32
Node 49
Node 48
3 - 30