9.3.33 WARNING/ALARM 34, Fieldbus Communication Fault
Cause
The fieldbus on the communication option card is not working.
9.3.34 WARNING/ALARM 35, Option Fault
Cause
An option alarm is received. The alarm is option-specific. The most likely cause is a power-up or a communication fault.
9.3.35 WARNING/ALARM 36, Mains Failure
Cause
This warning/alarm is only active if the supply voltage to the drive is lost and parameter 14-10 Mains Failure is not set to [0] No Function.
Troubleshooting
Check the fuses to the drive and mains supply to the unit.
9.3.36 ALARM 37, Phase Imbalance
Cause
There is a current imbalance between the power units.
9.3.37 ALARM 38, Internal Fault
Cause
When an internal fault occurs, a code number defined in
Troubleshooting
Cycle power.
Check that the option is properly installed.
Check for loose or missing wiring.
It may be necessary to contact the Danfoss supplier or service department. Note the code number for further troubleshooting
directions.
Table 73: Internal Fault Codes
Number
Text
0
The serial port cannot be initialized. Contact the Danfoss supplier or Danfoss service department.
256-258
The power EEPROM data is defective or too old. Replace the power card.
512-519
Internal fault. Contact the Danfoss supplier or Danfoss service department.
783
Parameter value outside of minimum/maximum limits.
140 | Danfoss A/S © 2018.10
table 73
is shown.
Maintenance, Diagnostics, and
Troubleshooting
AQ262141314214en-000101 / 130R0880