Operating Guide | VLT® HVAC Drive FC 102
Type of fault
Alarm
Trip lock
Status
0.0Hz
Earth Fault [A14]
Auto Remote Trip
Illustration 68:
Alarm Example
9.3.2 WARNING 1, 10 Volts Low
Cause
The control card voltage is less than 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is
overloaded. Maximum 15 mA or minimum 590 Ω.
A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition.
Troubleshooting
Remove the wiring from terminal 50. If the warning clears, the problem is with the wiring. If the warning does not clear, replace the
control card.
9.3.3 WARNING/ALARM 2, Live Zero Error
Cause
This warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is
less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this
condition.
Troubleshooting
Check connections on all analog mains terminals.
-
Control card terminals 53 and 54 for signals, terminal 55 common.
Check that the drive programming and switch settings match the analog signal type.
Danfoss A/S © 2018.10
Warning indicator light
Off
On
1(1)
0.000kW
0.0Hz
0
Alarm indicator light
On (flashing)
On (flashing)
0.00A
Maintenance, Diagnostics, and
Troubleshooting
AQ262141314214en-000101 / 130R0880 | 131

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents