Danfoss VLT HVAC Drive FC 102 Operating Manual page 161

110-800 kw, enclosures d9h-d10h and e5h-e6h
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Operating Guide | VLT® HVAC Drive FC 102
FC 102
- Mains with contactor
2
[mm
(AWG)]
2
- Motor [mm
(AWG)]
Drive module power
loss at 600 V [W]
(1) (2) (3)
Drive module power
loss at 690 V [W]
(1) (2) (3)
Drive efficiency
(2)
Output frequency [Hz]
(4)
Heat sink overtempera-
ture trip [°C (°F)]
Control card overtem-
perature trip [°C (°F)]
PHF overtemperature
trip [°C (°F)]
dU/dt filter overtemper-
ature trip [°C (°F)]
Sine-wave filter over-
temperature trip [°C
(°F)]
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/
knowledge-center/energy-efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see the Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also Input Power Option Losses.
4
If using an output filter, the output frequency is limited further. See the Motor Output (U, V, W) section.
Table 78: Electrical Data, Mains Supply 3x525–690 V AC
FC 102
Normal overload
110% torque for a duration of 60 s.
Typical shaft output at 550 V [kW]
Typical shaft output at 575 V [hp]
Typical shaft output at 690 V [kW]
Enclosure size
Danfoss A/S © 2018.10
N110
N132
N160
2x95
2x95
2x95
(2x3/0
(2x3/0
(2x3/0
mcm)
mcm)
mcm)
2x95
2x95
2x95
(2x3/0
(2x3/0
(2x3/0
mcm)
mcm)
mcm)
1740
2101
2649
1798
2167
2740
0.98
0.98
0.98
0–590
0–590
0–590
110 (230)
110 (230)
110 (230)
80 (176)
80 (176)
80 (176)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
N500
NO
400
500
500
E5h
N200
N250
2x185
2x185
(2x350
(2x350
mcm)
mcm)
2x185
2x185
(2x350
(2x350
mcm)
mcm)
3074
3723
3175
3851
0.98
0.98
0–590
0–590
110 (230)
110 (230)
80 (176)
80 (176)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
N560
N630
NO
NO
450
500
600
650
560
630
E5h
E6h
Specifications
N315
N400
2x185
2x185
(2x350
(2x350
mcm)
mcm)
2x185
2x185
(2x350
(2x350
mcm)
mcm)
4465
5028
4614
5155
0.98
0.98
0–590
0–590
110 (230)
110 (230)
80 (176)
80 (176)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
N710
N800
NO
NO
560
670
750
950
710
800
E6h
E6h
AQ262141314214en-000101 / 130R0880 | 161
N450
4x120
(4x250
mcm)
4x120
(4x250
mcm)
6062
5939
0.98
0–590
110 (230)
80 (176)
150 (302)
150 (302)
150 (302)