Operating Guide | VLT® HVAC Drive FC 102
9.3.79 ALARM 81, CSIV Corrupt
Cause
The CSIV file has syntax errors.
9.3.80 ALARM 82, CSIV Parameter Error
Cause
CSIV failed to initialize a parameter.
9.3.81 ALARM 83, Illegal Option Combination
Cause
The mounted options are incompatible.
9.3.82 ALARM 84, No Safety Option
Cause
The safe option was removed without applying a general reset.
Troubleshooting
Reconnect the safety option.
9.3.83 ALARM 85, Dang Fail PB
Cause
PROFIBUS/PROFIsafe error.
9.3.84 ALARM 88, Option Detection
Cause
A change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has
been changed.
Troubleshooting
To apply the change, enable option layout changes in parameter 14-89 Option Detection.
Alternatively, restore the correct option configuration.