Table 80: Line Reactor Configuration for D9h–D10h and E5h–E6h Enclosures, 525–690 V
Enclosure
D9h
D10h
E5h
E6h

10.7.3 dU/dt Filter Specifications

Voltage rating
Nominal current @ 50 Hz
Motor frequency derating, 50 Hz
Motor frequency derating, 60 Hz
Motor frequency derating, 100 Hz
Minimum switching frequency
Maximum switching frequency
Overload capacity
Ambient temperature [°C (°F)]
Storage temperature [°C (°F)]
Transport temperature [°C (°F)]
Maximum ambient temperature with derating [°C (°F)]
Maximum altitude without derating [°C (°F)]
Noise level
1
The current ratings for the E5h and E6h enclosures are achieved by filter paralleling.
Table 81: dU/dt Filter Configurations for D9h–D10h and E5h–E6h Enclosures, 380–480 V
Enclosure
D9h
D9h
D9h
170 | Danfoss A/S © 2018.10
Model
N110
N132
N160
N200
N250
N315
N400
N450
N500
N560
N630
N710
N800
Model
Current rating [A]
N110
261
N132
261
N160
418
Line reactor [A]
225
225
225
315
315
2x225
2x225
2x315
2x315
2x315
3x225
3x315
3x315
150% for 60 s, every 10 minutes.
Filters required
1
1
1
AQ262141314214en-000101 / 130R0880
Specifications
3x380–690 V
(1)
Up to 590 A
Nominal
Nominal
0.75 x nominal
No limit
Nominal switching frequency
-10 (14) to +45 (113)
-25 (-13) to +60 (150)
-25 (-13) to +70 (158)
55 (131)
< drive module