Operating Guide | VLT® HVAC Drive FC 102

6 Pre-start Check List

6.1 Pre-start Check List
Motor
Confirm continuity of the motor by measuring ohm values on U–V (96–97), V–W (97–98), and W–U (98–96).
Confirm that the supply voltage matches the voltage of the drive and the motor.
Switches
Ensure that all switch and disconnect settings are in the proper positions.
Auxiliary equipment
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that reside on the input power side of the
drive or output side to the motor. Ensure that they are ready for full-speed operation.
Check function and installation of any sensors used for feedback to the drive.
Remove any power factor correction caps on motor.
Adjust any power factor correction caps on the mains side and ensure that they are dampened.
Cable/wire routing
Ensure that motor wiring, brake wiring (if equipped), and control wiring are separated or shielded or in 3 separate metallic
conduits for high-frequency interference isolation.
Control wiring
Check for broken or damaged wires and loose connections.
Check that control wiring is isolated from high-power wiring for noise immunity.
Check the voltage source of the signals, if necessary.
Use shielded or twisted pair cable.
Ensure that the shield is terminated correctly.
Input and output power wiring
Check for loose connections.
Check that motor and mains are in separate conduit or separated shielded cables.
Grounding
Make sure that a proper ground is used. Grounding to conduit or mounting the back panel to a metal surface is not a suitable
grounding.
Check for good ground connections that are tight and free of oxidation.
Fuses and circuit breakers
Check for proper fusing or circuit breakers.
Check that all fuses are inserted firmly and are in operational condition.
Check that all circuit breakers (if used) are in the open position.
Cooling clearance
Look for any obstructions in the airflow path.
Measure top and bottom clearance of the drive to verify that there is at least 225 mm (9 in) of clearance for adequate airflow.