Available languages

Step 7.
Network connection
Network/Fax/Phone surge port:
Connect a single modem/phone/fax line into surge-protected "IN"
outlet on the back panel of the UPS unit. Connect from "OUT" outlet to
the equipment with another modem/fax/phone line cable.
Step 8.
Disable and enable EPO function: Keep the pin 1 and pin 2
closed for UPS normal operation.
It's in closed status for
UPS normal operation.
Step 9.
Turn on the UPS: Press the ON/Mute button on the front panel
for two seconds to power on the UPS.
NOTE:
The battery charges fully during the first five hours of normal
operation. Do not expect full battery run capability during this initial
charge period.
12
To activate EPO
function, remove these
two screws.
Step 10.
Install software: For optimal computer system protection,
install UPS monitoring software to fully configure UPS
shutdown. Use supplied RS-232 or USB communication cable
to connect RS-232/USB port of UPS and RS-232/USB port of
PC. Install the UPS monitoring software from
power-software-download.com/viewpower.html
configure UPS shutdown.
5
Operations
5.1

Button operations

ON/MUTE
SELECT
ON/Mute Button
Turn on the UPS: Press and hold ON/Mute button for at least 2
seconds to turn on the UPS.
Mute the alarm: After the UPS is turned on in battery mode,
press and hold this button for at least 5 seconds to disable or
enable the alarm system. But it's not applied to the situations
when warnings or errors occur.
Up key: Press this button to display previous selection in UPS
setting mode.
Switch to UPS self-test mode: Press ON/Mute buttons
simultaneously for 5 seconds to enter UPS self-testing while in
AC mode, ECO mode, or converter mode.
OFF/Enter Button
Turn off the UPS: Press and hold this button for at least 2
seconds to turn off the UPS. The UPS will be in standby mode
under normal power or transfer to Bypass mode if the Bypass
setting is enabled.
Confirm selection key: Press this button to confirm selection in
UPS settings mode.