18
Battery Low
Over Load
Over input current
Battery No Connect
Over Charge
Site wiring fault
EPO
Temperature
Charger
Battery Fault
Bypass Out Range
Bypass frequency
unstable
EEPROM error
Battery
Replacement
5.5
UPS Settings
Parameter 1
1
There are two parameters to set up the UPS.
Parameter 1:
For program alternatives. Refer to the table below.
Parameter 2:
The settings options or values for each program.
Interface
Settings
01: Output voltage settings
Parameter 2: Output voltage:
200:
presents output voltage is 200Vac
208:
present output voltage is 208Vac
220:
present output voltage is 220Vac
230:
present output voltage is 230Vac
240:
present output voltage is 240Vac
NOTE: Derate capacity to 80% when
the output voltage is adjusted to
200VAC/208VAC.
02: Frequency Converter enable/disable
Parameter 2: Enable or disable converter
mode.
You may choose the following two op-
tions:
CF
ENA: converter mode enable
CF DIS:
converter mode disable (Default)
NOTE: Derate capacity to 80% when
Frequency Converter mode is enabled.
Parameter 2
2
19