10: Programmable outlets setting
Parameter 2: Set up backup time limits
for programmable outlets.
0-999:
minutes from 0-999 for programmable
outlets which connect to non-critical
devices on battery mode. (Default: 999).
11: Autonomy limitation setting
Parameter 2: Set up backup time on
battery mode for general outlets.
0-999:
from 0-999 for general outlets on battery
mode.
DIS:
and the backup time will depend on
battery capacity. (Default)
NOTE: When setting as "0", the backup
time will be only 10 seconds.
12: Battery total AH setting
Parameter 2:Set up the battery total AH
of the UPS.
7-999:
capacity from 7-999 in AH. Please set
the correct battery total capacity if
external battery bank is connected.
13: Maximum charger current setting
If you use external battery pack please
set the appropriate charging current
based on battery capacity used. Please
use the following table as reference:
22
setting the backup time limits in
setting the backup time in minutes
Disable the autonomy limitation
: setting the battery total
Battery capacity(AH)
7~20
20~40
40~60
60~80
80~100
100~150
NOTE: If you connect Battery Pack 2U for
Balder 1500 (PWUP-BP06PBA-AZ01B)
to Balder 1500 you should set maximum
charger current to 4A.
If you connect Battery Pack 2U for Balder
3000 (PWUP-BP12PBA-AZ01B) to Balder
3000 you should set maximum charger
current to 4A.
14: Charger Boost voltage setting
Parameter 2: Set up the charger boost
voltage.
2.25-2.40:
setting the charger boost
voltage from 2.25 V/cell to 2.40V/cell.
(Default: 2.36V/cell)
15: Charger Float voltage setting
Parameter 2: Set up the charger float
voltage.
2.20-2.33:
setting the charger float
voltage from 2.20 V/cell to 2.33V/cell.
(Default: 2.28V/cell)
16: EPO logic setting
Parameter 2: Set up the EPO function
control logic.
AO:
Active Open (Default). When AO is
selected as EPO logic, it will activate
EPO function with Pin 1 and Pin 2 in
open status.
AC:
Active Close. When AC is selected as
EPO logic, it will activate EPO function
with Pin 1 and Pin 2 in close status.
Total charging
current (A)
2
4
6
8
10
12
23