03: Output frequency settings
Parameter 2: You may set the initial fre-
quency on battery mode:
BAT 50:
BAT 60:
If converter mode is enabled, you may
choose the following output frequency:
CF 50:
CF 60:
04: ECO enable/disable
Parameter 2: Enable or disable ECO
function. You may choose the following
two options:
ENA:
DIS:
05: ECO voltage range setting
Parameter 2: Set the acceptable high
voltage point and low voltage point
for ECO mode by pressing Down key or
Up key.
HLS:
parameter 2.
The setting range in parameter 3 is from
+7V to +24V of the nominal voltage.
(Default: +12V)
LLS:
parameter 2.
The setting range in parameter 3 is from
-7V to -24V of the nominal voltage.
(Default: -12V)
06: Bypass enable/disable when UPS is off
Parameter 2: Enable or disable Bypass
function. You may choose the following
two options:
ENA:
DIS:
20
presents output frequency of 50Hz
presents output frequency of 60Hz
present output frequency is 50Hz
present output frequency is 60Hz
ECO mode enable
ECO mode disable (Default)
High loss voltage in ECO mode in
Low loss voltage in ECO mode in
Bypass enable
Bypass disable (Default)
07: Bypass voltage range setting
Parameter 2: Set the acceptable high
voltage point and acceptable low voltage
point for Bypass mode by pressing the
Down key or Up key.
HLS:
Bypass high voltage point
230-264:
setting the high voltage point
in parameter 3 from 230Vac to 264Vac.
(Default: 264Vac)
LLS:
Bypass low voltage point
170-220:
setting the low voltage point
in parameter 3 from 170Vac to 220Vac.
(Default: 170Vac)
08: Bypass frequency range setting
Parameter 2: Set the acceptable high
frequency point and acceptable low
frequency point for Bypass mode by
pressing the Down key or Up key.
HLS:
Bypass high frequency point
51-55Hz:
setting the frequency high
loss point from 51Hz to 55HZ(Default:
53.0Hz).
LLS:
Bypass low Frequency point
45-49Hz:
setting the frequency low loss
point from 45Hz to 49HZ(Default: 47.0Hz)
09: Programmable outlets enable/disable
Parameter 2: Enable or disable the
programmable outlets function.
You may choose the following two
options:
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable
(Default)
21