button for 5 seconds to enter UPS self-testing while in
AC mode, ECO mode, or converter mode.
OFF/Enter Button
Turn off the UPS: Press and hold this button for at
least 2 seconds to turn off the UPS. The UPS will be
in standby mode under normal power or transfer to
Bypass mode if the Bypass setting is enabled.
Confirm selection key: Press this button to confirm
selection in UPS settings mode.

Select Button

Switch LCD message: Press this button to change
the LCD message for input voltage, input frequency,
battery voltage, output voltage and output frequency.
It will return back to default display after a 10 seconds
pause.
Settings mode: Press and hold this button for 5 seconds
to enter UPS settings mode when the UPS is in standby
mode or bypass mode.
Down key: Press this button to display next selection in
UPS settings mode.
ON/Mute + Select Button
Switch to bypass mode: When the main power is normal,
press ON/Mute and Select buttons simultaneously for
5 seconds. Then the UPS will enter to bypass mode.
This action will be ineffective when the input voltage is
out of acceptable range.