ABB PROFIBUS FEX100-DP User Manual page 8

Watermaster electromagnetic flowmeter
Table of Contents

Advertisement

WaterMaster
Electromagnetic flowmeter
Abs. Idx /
Variable Name / Brief Description
Rel. Idx
DIAG_SIMUL_STATUS
Enables / Disables diagnosis simulation.
52 / 36
0: Disabled
1: Enabled
DP_ENABLED_FEAT_PROT
Extended PROFIBUS features to be supported.
53 / 37
1: ChkCfg
2: SetPrm
DIAG_CONDITION_IDX
Index of the alarm history item to be read back via the DIAG_DETAILS item.
0: None
1: Logic simulation selected on OP1
2: Pulse simulation selected on OP1
3: Logic simulation selected on OP1
4: Pulse simulation selected on OP2
5: Logic simulation selected on OP3
6: Low flow alarm
7: High flow alarm
8: Q > 103% Qmax
9: Simulation mode on
10: Tx. simulator / calibrator mode
11: At Qmax, volume display overrun <1600hrs
12: Totalizer reset
13: Intermittent sensor comms
15: Tx. memory fault detected
54 / 38
16: Sensor memory not detected
17: Tx. measurement suspended
18: Empty pipe
21: Open circuit electrode
22: Short circuit electrode
24: Installation fault/condition
25: Open circuit coil/wiring
26: Short circuit coil/wiring
27: Check cable+coil resistance
28: Transmitter hardware fault
29: Bad flow data
30: Accuracy warning?
31: OIML self-check limits exceeded
32: Measurement starting
34: Sensor setup not complete
35: Incompatible sensor
36: Tx. code memory fault
37: Tx. data memory fault
39: Alarm simulation active
40: Non-volatile summary alarm
DIAG_DETAILS
55 / 39
Alarm history of the alarm selected by the DIAG_CONDITION_IDX parameter.
Table 2.2 Slot 0 – Physical Block (Continued)
6
Access /
Data Type
Size
Store
Usage /
Transport
Unsigned 8
1
D
r,w / C / a
Unsigned 8
1
N
r,w / C / a
Unsigned 8
1
D
r,w / C / a
Diagnosis
14
D
r / C / a
Information
2 Parameter Tables
Default
Disabled
ChkCfg
SetPrm
None
IM/WMPBST–EN Rev. B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents