ABB PROFIBUS FEX100-DP User Manual page 39

Watermaster electromagnetic flowmeter
Table of Contents

Advertisement

WaterMaster
Electromagnetic flowmeter
Abs. Idx /
Variable Name / Brief Description
Rel. Idx
FACTORY_SENSOR_ZERO
106 / 90
Factory-set zero value.
Unit: mm/s
TRIM_ST
107 / 91
Trim factor.
Unit: %
SENSOR_CALIBRATION_TYPE
Sensor calibration type performed.
0: Retrofit
1: OIML Class 1
108 / 92
2: OIML Class 2
3: Special
4: OIML Certified Class 1
5: OIML Certified Class 2
6: Probe
7: NMI
8: Select
DRIVE_MODE
Drive mode currently in use.
0: User
1: 1
2: 2
3: 3
4: 4
5: 5
6: 6
7: 7
8: 8
109 / 93
9: 3A
10: 4A
11: 5A
12: 5B
13: 6A
14: 6B
15: 7A
16: 7B
17: 7C
18: 7D
19: 8A
20: 8B
21: 8C
EXCITATION_CURRENT
110 / 94
Coil current value.
Unit: mA
FACTORY_CUTOFF
111 / 95
Cutoff velocity set during calibration.
Unit: mm/s
FACTORY_CUTOFF_NUM_AVERAGING_SAMPLES
112 / 96
Number of samples used in averaging filter.
CALIBRATION_STATUS
Sensor calibration status.
113 / 97
0: Not Complete
1: Calibrated
VOLUME_FLOW_RANGE_LOWER
114 / 98
Dynamic lower limit for flow values.
Unit: TB1.VOLUME_FLOW_UNITS
Table 2.10 Slot 8 – Transducer Block 1 – Flow (Continued)
IM/WMPBST–EN Rev. B
Access /
Data Type
Size
Store
Usage /
Transport
Float
4
D
r / C / a
Float
4
D
r / C / a
Unsigned 8
1
D
r / C / a
Unsigned 8
1
D
r / C / a
Float
4
D
r / C / a
Float
4
D
r / C / a
Unsigned 8
1
D
r / C / a
Unsigned 8
1
D
r / C / a
Float
4
D
r / C / a
2 Parameter Tables
Default
0
0
OIML Class 1
5A
180
0
4
Not Complete
0.5
37

Hide quick links:

Advertisement

Table of Contents
loading