ABB PROFIBUS FEX100-DP User Manual page 34

Watermaster electromagnetic flowmeter
Table of Contents

Advertisement

WaterMaster
Electromagnetic flowmeter
Abs. Idx /
Variable Name / Brief Description
Rel. Idx
ZERO_POINT
User zero velocity value.
28 / 12
Min: -50
Max: 50
Unit: mm/s
ZERO_POINT_ADJUST
29 / 13
Starts a zero velocity adjustment.
ZERO_POINT_UNIT
30 / 14
Units of zero velocity (fixed to mm/s).
1062: mm/s
NOMINAL_SIZE
31 / 15
Size of the sensor in use.
Unit: TB1.NOMINAL_SIZE_UNITS
NOMINAL_SIZE_UNITS
Units used for pipe bore size.
32 / 16
1013: mm
1019: in
VOLUME_FLOW
33 / 17
Volume flow, primary system variable.
Unit: TB1.VOLUME_FLOW_UNITS
VOLUME_FLOW_UNITS
Volume flow units in use.
1347: m3/s
1348: m3/min
1349: m3/h
1350: m3/d
1351: l/s
1352: l/min
1353: l/h
1355: Ml/d
1356: ft3/s
1357: ft3/min
1358: ft3/h
1359: ft3/d
34 / 18
1362: ugal/s
1363: ugal/min
1364: ugal/h
1365: ugal/d
1454: kugal/min
1366: Mugal/d
1367: igal/s
1368: igal/min
1369: igal/h
1370: igal/d
1371: bbl/s
1372: bbl/min
1373: bbl/h
1374: bbl/d
1563: ml/min
1577: ml/s
1635: hl/h
VOLUME_FLOW_LO_LIMIT
35 / 19
Absolute value of the lower range value (volume flow) of the sensor.
Unit: TB1.VOLUME_FLOW_UNITS
Table 2.10 Slot 8 – Transducer Block 1 – Flow (Continued)
32
Access /
Data Type
Size
Store
Usage /
Transport
Float
4
S
r,w / C / a
Unsigned 8
1
N
r,w / C / a
Unsigned 16
2
S
r,w / C / a
Float
4
S
r / C / a
Unsigned 16
2
S
r,w / C / a
101
5
D
r / O / a
Unsigned 16
2
S
r,w / C / a
Float
4
S
r,w / C / a
2 Parameter Tables
Default
0
0
mm/s
20
mm
0
m3/h
0
IM/WMPBST–EN Rev. B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents