ABB PROFIBUS FEX100-DP User Manual page 29

Watermaster electromagnetic flowmeter
Table of Contents

Advertisement

WaterMaster
Electromagnetic flowmeter
Abs. Idx /
Variable Name / Brief Description
Rel. Idx
HI_LIM
39 / 23
Upper limit value for alarms with the same engineering unit as that of the OUT parameter.
If the measured variable is equal to or higher than the upper limit value, the State Bits in
the Status Byte of OUT and in the FB parameter ALARM_SUM are set to 1.
UNUSED
40 / 24
Unused parameter.
LO_LIM
41 / 25
Lower limit value for alarms with the same engineering unit as that of the OUT parameter.
If the measured variable is equal to or lower than the lower limit value, the State Bits in
the Status Byte of OUT and in the FB parameter ALARM_SUM are set to 1.
UNUSED
42 / 26
Unused parameter.
LO_LO_LIM
43 / 27
Lower limit value for alarms with the same engineering unit as that of the OUT parameter.
If the measured variable is equal to or lower than the lower limit value, the State Bits in
the Status Byte of OUT and in the FB parameter ALARM_SUM are set to 1.
UNUSED
44 / 28
Unused parameter.
UNUSED
45 / 29
Unused parameter
HI_HI_ALM
46 / 30
The state of the upper limit of an alarm and the related time stamp. The time stamp
expresses the time the measured variable has been equal or higher than the upper limit
of the alarm.
HI_ALM
47 / 31
The state of the upper limit of an alarm and the related time stamp. The time stamp
expresses the time the measured variable has been equal or higher than the upper limit
of the alarm.
LO_ALM
48 / 32
The state of the lower limit of an alarm and the related time stamp. The time stamp
expresses the time at which the measured variable has been equal to or lower than the
lower limit of the alarm.
LO_LO_ALM
49 / 33
The state of the lower limit of an alarm and the related time stamp. The time stamp
expresses the time at which the measured variable has been equal to or lower than the
lower limit of the alarm.
SIMULATE
50 / 34
For commissioning and test purposes the input value from the Transducer Block to the
block can be simulated. Note that the Transducer block is disconnected from the block
when the SIMULATE parameter is in use.
OUT_UNIT_TEXT
51 / 35
If the unit of the OUT parameter is not available in the list of PROFIBUS Unit Codes, the
user can write the specific text in this parameter. The unit code is then set to 'textual unit
definition'.
Table 2.8 Slot 6 – Analog Input 4 – Diagnostic Signal (Continued)
IM/WMPBST–EN Rev. B
Access /
Data Type
Size
Store
Usage /
Transport
Float
4
S
r,w / C / a
Float
4
S
r,w / C / a
Float
4
S
r,w / C / a
DS-39
16
D
r / C / a
DS-39
16
D
r / C / a
DS-39
16
D
r / C / a
DS-39
16
D
r / C / a
DS-50
6
S
r,w / C / a
OctetString
16
S
r,w / C / a
2 Parameter Tables