ABB PROFIBUS FEX100-DP User Manual page 47

Watermaster electromagnetic flowmeter
Table of Contents

Advertisement

WaterMaster
Electromagnetic flowmeter
Abs. Idx /
Rel. Idx
RESET_ALL_VOLUME
30 / 14
Resets all volume totalizers.
DO1_PULSES
31 / 15
Output frequency of Digital Output 1.
Unit: Hz
DO2_PULSES
32 / 16
Output frequency of Digital Output 2.
Unit: Hz
DO1_STATE
Output state of Logic Output 1.
33 / 17
0: Open
1: Closed
DO2_STATE
Output state of Logic Output 2.
34 / 18
0: Open
1: Closed
DO3_STATE
Output state of Logic Output 3.
35 / 19
0: Open
1: Closed
DO1_DO2_FUNCTION
Digital Outputs 1 and 2 operating mode.
36 / 20
0: Pulse F/Pulse R
1: Pulse F/Logic
2: Pulse FR/Logic
3: Logic / Logic
DO1_LOGIC_SIGNAL_SOURCE
Signal source for Logic Output 1.
37 / 21
0: No Function
1: F/R Signal
2: Digital Out Alarm
DO1_GENERAL_ALARM_BEHAVIOUR
General alarm behavior for Logic Output 1.
38 / 22
0: Off
1: On
DO1_MIN_ALARM_BEHAVIOUR
Min. Flow alarm behavior for Logic Output 1.
39 / 23
0: Off
1: On
DO1_MAX_ALARM_BEHAVIOUR
Max. Flow alarm behavior for Logic Output 1.
40 / 24
0: Off
1: On
DO1_EMPTY_PIPE_BEHAVIOUR
Empty Pipe alarm behavior for Logic Output 1.
41 / 25
0: Off
1: On
Table 2.12 Slot 10 – Transducer Block 3 – Special Function (Continued)
IM/WMPBST–EN Rev. B
Variable Name / Brief Description
Access /
Data Type
Size
Store
Usage /
Transport
Unsigned 8
1
D
r,w / C / a
Float
4
D
r / C / a
Float
4
D
r / C / a
Unsigned 8
1
D
r / C / a
Unsigned 8
1
D
r / C / a
Unsigned 8
1
D
r / C / a
Unsigned 8
1
S
r,w / C / a
Unsigned 8
1
S
r,w / C / a
Unsigned 8
1
S
r,w / C / a
Unsigned 8
1
S
r,w / C / a
Unsigned 8
1
S
r,w / C / a
Unsigned 8
1
S
r,w / C / a
2 Parameter Tables
Default
0
0
Open
Open
Open
Pulse FR/Logic
No Function
Off
Off
Off
Off
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents