Word Data (Read/Write): Function Code 03 (H), 06 (H), 10 (H)] - Fuji Electric PXG-9 Communication Instruction Manual

Digtal controller micro controller x communication function (rs-485 modbus)
Hide thumbs Also See for PXG-9:
Table of Contents

Advertisement

Word Data (read/write): function code [03 (H), 06 (H), 10 (H)]
Operation (Ch1)
Parameter
Parameter
Contents
display
name
M M M M a a a a n n n n
MAn
Switches to manual mode 0088
"
"
S S S S T T T T b b b b Y Y Y Y
STbY
Switches between RUN
"
"
and standby
r r r r E E E E M M M M
rEM
Switches to remote mode
"
"
P P P P r r r r G G G G
PrG
Ramp/soak controls
"
"
Command
A A A A t t t t
AT
Auto-tuning
"
"
run command
L L L L A A A A C C C C h h h h
LACh
Cancels the DO output
"
"
latch Command
S S S S v v v v n n n n
Svn
Selectable SV numbers
"
"
P P P P L L L L n n n n 1 1 1 1
PLn1
Currently selected PID No. 00F3
"
"
A A A A L L L L 1 1 1 1
AL1
ALM1 set value or A1-L
"
"
A A A A L L L L 1 1 1 1 L L L L
AL1L
AL1L set value
"
"
A A A A L L L L 1 1 1 1 h h h h
AL1h
AL1h set value
"
"
A A A A L L L L 2 2 2 2
AL2
ALM2 set value or A2-L
"
"
A A A A L L L L 2 2 2 2 L L L L
AL2L
AL2L set value
"
"
A A A A L L L L 2 2 2 2 h h h h
AL2h
AL2h set value
"
"
A A A A L L L L 3 3 3 3
AL3
ALM3 set value or A3-L
"
"
A A A A L L L L 3 3 3 3 L L L L
AL3L
AL3L set value
"
"
A A A A L L L L 3 3 3 3 h h h h
AL3h
AL3h set value
"
"
A A A A L L L L 4 4 4 4
AL4
ALM4 set value or A4-L
"
"
A A A A L L L L 4 4 4 4 L L L L
AL4L
AL4L set value
"
"
Resistor Number
Relative
Type
Engineering
address
Internal
unit
40121
41121
Word
H
0003
40004
41004
Word
H
0084
40117
41117
Word
H
0061
40082
41082
Word
H
0004
40005
41005
Word
H
00B0
40161
41161
Word
H
00F2
40221
41221
Word
H
40222
41222
Word
H
003B
40044
41044
Word
H
00B2
40163
41163
Word
H
00B3
40164
41164
Word
H
003C
40045
41045
Word
H
00B9
40170
41170
Word
H
00BA
40171
41171
Word
H
003D
40046
41046
Word
H
00C0
40177
41177
Word
H
00C1
40178
41178
Word
H
00C7
40184
41184
Word
H
00C7
40184
41184
Word
H
– 43 –
Written data
Read data
range
0: oFF (during auto)
0: oFF (auto)
1: on (during manual)
1: on (manual)
0: oFF (during RUN)
1: on (during standby)
0: LoCL (during Local)
0: LoCL (Local)
1: rEM (during Remote)
1: rEM (Remote)
0: oFF (during stop)
0: oFF (stop)
1: rUn (during run)
1: rUn (run)
2: hLd (during hold)
2: hLd (hold)
0: oFF
1: rUn
2: Low
0: oFF
1: rST (latch reset)
0: Sv0 (Local SV)
1: Sv1 (SV = SV-1)
2: Sv2 (SV = SV-2)
3: Sv3 (SV = SV-3)
4: Sv4 (SV = SV-4)
5: Sv5 (SV = SV-5)
6: Sv6 (SV = SV-6)
7: Sv7 (SV = SV-7)
8: di : SV = choose Di
0: PID0 (PID group local)
1: PID1 (PID group No. 1)
2: PID2 (PID group No. 2)
3: PID3 (PID group No. 3)
4: PID4 (PID group No. 4)
5: PID5 (PID group No. 5)
6: PID6 (PID group No. 6)
7: PID7 (PID group No. 7)
8: di (PID group Di selection)
0% to 100% FS
0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
0% to 100% FS
0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
0% to 100% FS
0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
0% to 100% FS
0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
Factory
Dependent
Setting
on range
oFF
oFF
LoCL
oFF
oFF
oFF
Chapter
Sv0
7
PID0
10°C
10°C
10°C
10°C