Fuji Electric PXG-9 Communication Instruction Manual page 39

Digtal controller micro controller x communication function (rs-485 modbus)
Hide thumbs Also See for PXG-9:
Table of Contents

Advertisement

Example of Transmitting a Message (Internal Calculation Data)
The message is composed as follows when writing the following PID parameters to station number 1.
P = 100.0 (= 1000D = 03E8H)
I = 10 (= 100D = 0064)
D = 5.0 (= 50D = 0032H)
• Parameter "P P P P " relative address: 0005H, Data number: 03H
Command Message (bytes)
Station No.
Function Code
Specified Write
Upper number
Number (Relative
Lower number
Address)
No. of Words to
Upper number
Write
Lower number
No. of Bytes to Write
First Word Data to
Upper number
Write
Lower number
Next Word Data to
Upper number
Write
Lower number
Last Word Data to
Upper number
Write
Lower number
CRC Data
Upper number
Lower number
The decimal point cannot be included in the sent data, so data such as "100.0" above is sent as "1000".
Point
Refer to
For each type of send data format, see "Chapter 7, Address
Map and Data Configuration" (p. 39).
Master
Slave
01H
10H
00H
05H
00H
03H
06H
03H
E8H
00H
64H
00H
32H
56H
BEH
– 37 –
Response Message (bytes)
Station No.
Function Code
Specified Write
Upper number
Number
Lower number
(Relative Address)
Upper number
Write Specification
State
Lower number
Upper number
CRC Data
Lower number
01H
10H
00H
Chapter
6
05H
00H
03H
90H
09H