Digtal controller micro controller x communication function (rs-485 modbus)
Hide thumbs Also See for PXG-9:
Table of Contents

Advertisement

Example of Transmitting a Message
This example explains how to set PID parameter "P" to 100.0 (1000D = 03E8H) on station number 1.
Parameter "P" relative address:
Command Message (bytes)
Station No.
Function Code
Specified Write
Upper number
Number
Lower number
(Relative Address)
Upper number
Word Data to Write
Lower number
Upper number
CRC Data
Lower number
For more about the internal calculation value, engineering unit, and decimal point see "Transmission Data
Point
Format" (p. 40).
0005H (internal calculation value table)
03EDH (initial value table)
Master
01H
06H
00H
05H
03H
E8H
99H
75H
– 35 –
Slave
Response Message (bytes)
Station No.
Function Code
Specified Write
Number
(Relative Address)
Write Specification
State
CRC Data
01H
06H
Upper number
00H
Lower number
05H
Upper number
03H
Lower number
E8H
Upper number
99H
Lower number
75H
Chapter
6