10.2 PROFINET
10.2.6

Configuring a CPU and PROFINET IO device

10.2.6.1

Adding a PROFINET IO device

Adding a PROFINET IO device
In the "Devices and networks" portal, use the hardware catalog to add PROFINET IO
devices.
Note
To add a PROFINET IO device, you can use STEP 7 Professional or Basic, V11 or greater.
For example, expand the following containers in the hardware catalog to add an ET200S IO
device: Distributed I/O, ET200S, Interface modules, and PROFINET. You can then select the
interface module from the list of ET200S devices (sorted by part number) and add the
ET200S IO device.
Table 10- 26 Adding an ET200S IO device to the device configuration
Insert the IO device
You can now connect the PROFINET IO device to the CPU:
1. Right-click the "Not assigned" link on the device and select "Assign new IO controller"
from the context menu to display the "Select IO controller" dialog.
2. Select your S7-1200 CPU (in this example, "PLC_1") from the list of IO controllers in the
project.
3. Click "OK" to create the network connection.
10.2.6.2

Configuring logical network connections between a CPU and a PROFINET IO device

Configuring logical network connections
After you configure the rack with the CPU, you are now ready to configure your network
connections.
In the "Devices and networks" portal, use the "Network view" to create the network
connections between the devices in your project. To create a PROFINET connection, click
the green (PROFINET) box on the first device, and drag a line to the PROFINET box on the
second device. Release the mouse button and your PROFINET connection is joined.
558
Result
S7-1200 Programmable controller