A.9 Thermocouple and RTD signal modules (SMs)
Table A- 170 Noise reduction and update times for the SM 1231 Thermocouple
Rejection frequency selection
400 Hz (2.5 ms)
60 Hz (16.6 ms)
50 Hz (20 ms)
10 Hz (100 ms)
To maintain module resolution and accuracy when 400 Hz rejection is selected, the integration time is 10 ms. This
1
selection also rejects 100 Hz and 200 Hz noise.
It is recommended for measuring thermocouples that a 100 ms integration time be used. The
use of smaller integration times will increase the repeatability error of the temperature
readings.
Note
After power is applied, the module performs internal calibration for the analog-to-digital
converter. During this time the module reports a value of 32767 on each channel until valid
data is available on that channel. Your user program may need to allow for this initialization
time. Because the configuration of the module can vary the length of the initialization time,
you should verify the behavior of the module in your configuration. If required, you can
include logic in your user program to accommodate the initialization time of the module.
Representation of analog values for Thermocouple Type J
A representation of the analog values of thermocouples type J is shown in the table below.
Table A- 171 Representation of analog values of thermocouples type J
Type J in °C
> 1450.0
1450.0
:
1200.1
1200.0
:
-150.0
< -150.0
Faulty wiring (for example, polarity reversal, or open inputs) or sensor error in the negative
1
range (for example, wrong type of thermocouple) may cause the thermocouple module to
signal underflow.
924
Integration time
10 ms
1
16.67 ms
20 ms
100 ms
Units
Decimal
Hexadecimal
32767
7FFF
14500
38A4
:
:
12001
2EE1
12000
2EE0
:
:
-1500
FA24
-32768
8000
4 Channel module update
time (seconds)
0.143
0.223
0.263
1.225
Type J in °F
Decimal
> 2642.0
32767
2642.0
26420
:
:
2192.2
21922
2192.0
21920
:
:
-238.0
-2380
< -238.0
-32768
System Manual, 03/2014, A5E02486680-AG
8 Channel module update
time (seconds)
0.285
0.445
0.525
2.450
Units
Range
Hexadecimal
7FFF
Overflow
6734
Overrange
:
55A2
55A0
Rated range
:
F6B4
8000
Underflow