Next, select "6ES7 151-1BA02-0AB0" (IM151-1 HF) from the list of part numbers, and add
the ET200 S DP slave as shown in the figure below.
Table 10- 29 Adding an ET200 S DP slave to the device configuration
Insert the DP slave
10.3.3.2

Configuring logical network connections between two PROFIBUS devices

After you configure the CM 1243-5 (DP master) module, you are now ready to configure your
network connections.
In the Devices and Networks portal, use the "Network view" to create the network
connections between the devices in your project. To create the PROFIBUS connection,
select the purple (PROFIBUS) box on the first device. Drag a line to the PROFIBUS box on
the second device. Release the mouse button and your PROFIBUS connection is joined.
Refer to "Device Configuration: Creating a network connection" (Page 149) for more
information.
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
Communication
10.3 PROFIBUS
Result