Sm 1223 Digital Input/Output Vdc Specifications - Siemens S7-1200 System Manual

Hide thumbs Also See for S7-1200:
Table of Contents

Advertisement

Technical specifications
A.7 Digital signal modules (SMs)
A.7.4

SM 1223 digital input/output VDC specifications

Table A- 123 General specifications
Model
Order number
Dimensions W x H x D (mm)
Weight
Power dissipation
Current consumption (SM Bus)
Current consumption (24 VDC)
Table A- 124 Digital inputs
Model
Number of inputs
Type
Rated voltage
Continuous permissible voltage
Surge voltage
Logic 1 signal (min.)
Logic 0 signal (max.)
Isolation (field side to logic)
Isolation groups
Filter times
Number of inputs on simultaneously
Cable length (meters)
900
SM 1223
SM 1223
DI 8 x 24 VDC, DQ
DI 16 x 24 VDC,
8 x Relay
DQ 16 x Relay
6ES7 223-1PH32-
6ES7 223-1PL32-
0XB0
0XB0
45 x 100 x 75
70 x 100 x 75
230 grams
350 grams
5.5 W
10 W
145 mA
180 mA
4 mA / Input used
11 mA / Relay coil used
SM 1223
SM 1223
DI 8 x 24 VDC, DQ
DI 16 x 24 VDC,
8 x Relay
DQ 16 x Relay
8
16
Sink/Source (IEC Type 1 sink)
24 VDC at 4 mA, nominal
30 VDC max.
35 VDC for 0.5 sec.
15 VDC at 2.5 mA
5 VDC at 1 mA
500 VAC for 1 minute
2
2
0.2, 0.4, 0.8, 1.6, 3.2, 6.4, and 12.8 ms, selectable in groups of 4
8
8 (no adjacent
points) at 60 °C
horizontal or
50 °C vertical
16 at 55 °C
horizontal or
45 °C vertical
500 m shielded, 300 m unshielded
SM 1223
SM 1223
DI 8 x 24 VDC, DQ
DI 16 x 24 VDC,
8 x 24 VDC
DQ 16 x 24 VDC
6ES7 223-1BH32-
6ES7 223-1BL32-
0XB0
0XB0
45 x 100 x 75
70 x 100 x 75
210 grams
310 grams
2.5 W
4.5 W
145 mA
185 mA
150 mA
200 mA
SM 1223
SM 1223
DI 8 x 24 VDC, DQ
DI 16 x 24 VDC,
8 x 24 VDC
DQ 16 x 24 VDC
8
16
2
2
8
16
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG

Advertisement

Table of Contents
loading

Table of Contents