Technology instructions
9.2 PID control
Table 9- 20
Sample configuration settings for the PID_3Step instruction
Settings
Basic
Controller type
Invert the control logic
Activate mode after
CPU restart
Input
Output
Feedback
Process
Scales both the range and the limits for the process value. If the process value goes below the low limit or
value
above the high limit, the PID loop goes to inactive mode and sets the output value to 0.
To use Input_PER, you must scale the analog process value (input value).
Actuator
Motor transition
time
Minimum ON time
Minimum OFF
time
438
Description
Selects the engineering units.
Allows selection of a reverse-acting PID loop.
If not selected, the PID loop is in direct-acting mode, and the output of PID loop
increases if the input value < setpoint).
If selected, the output of the PID loop increases if the input value > setpoint.
Restarts the PID loop after it is reset or if an input limit has been exceeded and
returned to the valid range.
Set Mode to: Defines the mode that the user wants the PID to go to after restart.
Selects either the Input parameter or the Input_PER parameter (for analog) for the
process value. Input_PER can come directly from an analog input module.
Selects either to use the digital outputs (Output_UP and Output_DN) or to use the
analog output (Output_PER) for the output value.
Selects the type of device status returned to the PID loop:
No feedback (default)
Feedback
Feedback_PER
Sets the time from open to close for the valve. (Locate this value on the data sheet or
the faceplate of the valve.)
Sets the minimum movement time for the valve. (Locate this value on the data sheet or
the faceplate of the valve.)
Sets the minimum pause time for the valve. (Locate this value on the data sheet or the
faceplate of the valve.)