Deviations and Advisories

There are two types of errors that can occur. Errors
are indicated on the display.
Deviations, indicated by
not immediately.
Advisories, indicated by
attention.
If a deviation or advisory occurs, the system
continues running. The error code and the
or the
flash on the screen. If multiple alarms
occur, F2 and F3 have higher priority than MF. They
will appear first and must be cleared first.
Icon
and
Code
Advisory alarm. If enabled, the
maintenance totalizer alarm displays
MF
when the user-set maintenance target
value is reached.
Deviation alarm. If enabled, the flow
rate low alarm displays when the
F2
flow rate is lower than the user set
minimum.
Deviation alarm. If enabled, the flow
rate high alarm displays when the
F3
flow rate is higher than the user set
maximum.
3A2614H
, require attention, but
, do not require
Deviations and Advisories
Description
Alarm Log Logic: If Alarm Auto Clear is enabled,
the system will not log the same alarm twice. For
example, if the system goes back forth between low
flow (F2) and normal, the system will log this error
only once, to keep the log from filling up before the
operator corrects the condition.
If Alarm Auto Clear is not enabled, each alarm will
log only once if the operator corrects the condition
and then clears the alarm. The alarm will log twice
if the operator clears the alarm before correcting the
condition.
The following table explains the error type that is
associated with each error code and icon.
How to Correct and Clear
Reset Maintenance Totalizer to zero (see
Setup Screen 1, page
26). Perform maintenance.
Press
to clear alarm. Alarm will not clear until
Maintenance Totalizer has been reset to zero.
Adjust flow rate, reset minimum flow target (see
Setup Screen 3, page
27), or disable alarm (see
Setup Screen 4, page
28).
Press
to clear screen. The alarm will not clear if the
flow rate is still lower than the user set target.
Adjust flow rate, reset maximum flow target (see
Setup Screen 3, page
27), or disable alarm (see
Setup Screen 4, page
28).
Press
to clear alarm. The alarm will not clear if the
flow rate is still higher than the user set target.
Deviations and Advisories
31