Jog - Toshiba TOSVERT-130G2+ Operation Manual

High performance transistor inverter igbt digital series
Table of Contents

Advertisement

8.3.3

Jog

The jog frequency is immediately output regardless of the predetermined
acceleration time. The jog frequency (JOG) and the type of jog stop pattern
(J.StP) must be pre-selected.
Function Function
No.
Name
6
Jog drive frequency
Jog stop control
DC injection starting
2ND
frequency
1
DC injection voltage
DC injection time
The following table identifies the STOP pattern and the next table illustrates a
JOG RUN in which the parameters "JOG" and "J.Stp" equal 5Hz and 1,
respectively.
0
Motor will decelerate to a stop at the rate of DEC1, or DEC2, (dependent upon SEL2).
1
Motor will coast to a stop.
2
Motor will have DC injection applied based upon the DC injection parameters located
in the 2nd Function #1.
Key
The inverter must be placed in the monitor mode and stopped before
MON
activating the jog feature.
2ND
0
Engages the jog feature.
Sets a forward run jog.
Sets a reverse run jog.
RUN
When held down the inverter will run at the preset jog speed.
RUN
When released the motor coasts to a stop (J.StP=1).
CLR
Disables the jog feature. The inverter returns to the monitor mode.
or
STOP
Function Parameters
Adjustment
Display
Range
0 to 20
0: Deceleration stop
1: Coast stop
2: DC injection stop
0.0 to 10
0 to 20
0.0 to 5
Jogging Stop Pattern
Pattern
Activating the JOG Feature
Action
8 - 7
TOSHIBA
Factory
Error
Unit
Set
Message
Hz
5
0
Hz
0
%
0
sec
0
Display
Ref.
Page
8-23
8-23
8-27
8-27
8-27