Toshiba TOSVERT-130G2+ Operation Manual page 13

High performance transistor inverter igbt digital series
Table of Contents

Advertisement

TOSHIBA
3.0
Standard Specifications (Cont'd)
ITEM
Control
Control Method
Output voltage regulation
Output frequency
Frequency setting
resolution
Frequency accuracy
Voltage/frequency
characteristics
Frequency setting signals
Output frequency
characteristics of IV
terminal input signal
Frequency jump
Upper/lower limit
frequencies
PWM carrier frequency
switching
Operating
Acceleration/deceleration
functions
time
Electrical braking
Forward or reverse run
Jogging run
Multispeed run
Automatic fault latch reset
Soft stall
Automatic restart
Programmable RUN
patterns
Protection
Protective functions
Electronic thermal
characteristics
Reset
*
Consult the factory for applications above 80 Hz.
STANDARD SPECIFICATIONS
Sinusoidal PWM control
Same as power line.
0.5 to 400Hz (0.1 to 80Hz setting when shipped); maximum
frequency range is 30 to 400Hz
0.1Hz: Operating panel input; 0.03Hz: Analog input; 0.01Hz:
Input through computer interface (against a 60Hz)
±0.5% (at 25°C; ±10°C) against the maximum frequency
Either constant V/f or second-order nonlinear mode for variable
torque. "Max voltage" frequency adjustment (25 to 400Hz), voltage
boost adjustment (0 to 30%), start-up frequency adjustment
(0 to 10Hz)
3k ohms potentiometer (a 1k to 10k ohms-rated potentiometer
can be connected). 0 to 10Vdc (input impedance: 30k ohms), 0 to
5Vdc (15k ohms), 4 to 20mAdc (250 ohms)
Can be set to an arbitrary characteristic by setting 2 points.
3-point setting; setting jump frequency and band width
Upper limit frequency: 0 to maximum frequency
Lower limit frequency: 0 to upper limit frequency
Adjusted in the range of 0.5kHz to 3kHz
0.1 to 6000 seconds, switching of acceleration time 1 or 2,
selection of S-shaped 1 or 2, or selection of acceleration/
deceleration patterns
G2+2010 to G2+430K; IGBT7 dynamic braking
DC injection braking Start-up frequency adjustment (0 to 10Hz),
braking voltage adjustment (0 to 20%),
braking time adjustment (0 to 5 seconds)
Forward run when F-CC closed; reverse run when R-CC closed;
reverse run when both F-CC and R-CC closed; coasting stop
when ST-CC open; emergency coast stop by a command from
operating panel
Jogging run engaged when N.O. contact is closed. (adjustment
range 0 to 20Hz)
By opening and closing different combinations of CC, SS1, SS2,
and SS3, the set speed or seven preset speeds can be selected.
When a protective function is activated, the system checks main
circuit devices, and attempts the restart up to 5 times (deactivated
when shipped)
Sustains a run in overload mode (set at OFF when shipped)
Smoothly recovers a normal run of a free-running motor utilizing
motor speed detection control.
Allows setting of 7 different patterns of automatic operation
Stall prevention, current limit, overcurrent, overvoltage, short-
circuit at load, load-end ground fault, undervoltage, momentary
power interrupt, electronic thermal overload, main circuit over-
current at start-up, load-end overcurrent at start-up, regenerative
discharge resistor overcurrent or overload, fin overheat, and
emergency stop. Provisions for external fault signal.
Standard motor/constant torque V/f motor switching, and
electronic thermal stall prevention activating level adjustment
Resets inverter when N.O. contact is closed.
3 - 2
*