Operating Functions - Descriptions and Examples (Cont'd)
The three (3) parameters in 2nd Function 9 on the G2+ allow the user to do a number
of different setups. The access to the inverter can be totally locked out, or select
functions can be locked out. By using these three parameters the inverter can be
programmed to function in a number of different ways.
The following example shows how to Start-Stop the unit via the touch-pad only and
have the frequency set by an external source only by changes to the paramenters
located in 2nd function 9.
Key
The inverter must always be placed in the function mode before
MON
accessing any function.
When this key is pressed the inverter is placed into the second
2ND
function files.
When this key is pressed the inverter is placed into the second
9
function file number 9.
When this key is pressed the standard factory adjustment range
READ
setting of 7 is displayed.
When the keys 2 and WRT are pressed in order then the factory
2
adjustment range setting of 2 is written into memory replacing the
WRT
factory setting of 7.
When this key is pressed the second menu item under the 2nd 9
NEXT
functions is displayed.
When this key is pressed the standard factory adjustment range
READ
setting of 7 is displayed.
When the keys 1 and WRT are pressed in order then the factory
1
adjustment range setting of 1 is written into memory replacing the
factory setting of 7.
WRT
Returns the inverter to the original monitor mode.
MON
Note:
This setup accepts an external signal (4-20 mA, 0-5 VDC, & etc. ) through the terminal strip
and allows the user to start and stop the unit via the touch-pad.