Output Signals; Selectable Outputs - Toshiba TOSVERT-130G2+ Operation Manual

High performance transistor inverter igbt digital series
Table of Contents

Advertisement

TOSHIBA
8.5

Output Signals

The inverter provides terminals for outputting signals to external components. A number
of selectable "operating" output signals, as well as "fault" output signals, are available.
These output signal terminals are located on the terminal board. The terminals and type
of selections available are shown below.
Output Terminals
8.5.1
Function Function
No.
Name
8
Multifunction output
Low speed detection
Speed reach selection
2ND
3
Speed reach detection
range
Speed reach reference
Setting on 0.tb
0
LL, UL (for lower limit and upper limit frequency signal)
1
LOW, UL (for low speed and upper limit frequency signal)
2
LL, RCH (for lower limit frequency and speed reach signals)
3
LOW, RCH (for low speed and speed reach signals)
Selectable function output signals (open-collector with 50mAdc~24Vdc ratings)
Terminal
Outputs a signal when frequency is = or > the LL value.
LL
Outputs a signal when frequency is = UL value.
UL
LOW
Outputs a signal when frequency is = or > the LOW SPEED DETECTION VALUE "LF".
RCH
Outputs a signal based upon the selection of the RCH parameters rCH, rrCH, FrCH.
Upper/lower limit frequency signal output
Hz
UL
Output
frequency
LL
Output signals:
Across
UL-P24
Across
LL-P24
RCH
LOW
(UL)
(LL)

Selectable Outputs

Function Parameters
Adjustment
Display
Range
0: LL, UL
1: LOW, UL
2: LL, RCH
3: LOW, RCH
0.0 to Max. frequency
0: Complete ACC/DEC
1: Frequency reach reference
2.5 to 25
0.0 to Max. frequency
Terminal Output Signal Selections
TIME
ON
TIME
ON
TIME
FLA
FLB
Unit
Function
Function
Low speed/speed reach signal output with rCH=0
Hz
Output
frequency
LOW
Output signals:
Across
LOW-P24
Across
ON
RCH-P24
8 - 16
FLC
Factory
Error
Set
Message
3
Hz
0.5
0
Hz
2.5
Hz
0
ON
ON
Ref.
Page
8-24
8-28
8-28
8-28
8-28
TIME
TIME
TIME