PID Set Point Control (Cont'd)
READJUSTMENT
1) For faster response time set larger proportional gain, shorter integral gain and/or
shorter acceleration and deceleration times.
2) To stabilize the system adjust increase anti-hunting gain, increase lag-time constant
and/or slow the response time.
SPECIAL ADJUSTMENTS
1) The touch pad may be used to adjust the setpoint by changing the frequency
reference setting mode selection to touch pad only (2nd function # 9).
2) The touch pad may be used to start and stop the drive by changing the command
mode selection to touch pad only (2nd function # 9).
HAVING TROUBLE?
Please check the following list. These are things which will cause the PID loop in the
TOSVERT-130 G2+ to operate incorrectly.
1) FEEDBACK - Make sure that the feedback signal has the correct polarity. Make
sure that jumpers JP1 and JP2 (located on main control printed circuit board PCB1)
are correctly set.
2) SOFTWARE - Make sure that the inverter main software is Version 5.2 (see Section
7.5 "Status Monitoring").
3) SETPOINT - Make sure that the setpoint potentiometer is connected correctly or
that the keypad has been selected to adjust the setpoint.
4) START - Make sure that the drive is given a run command by either contact closure
or pressing the keypad start button.
IF ANY PROBLEMS OCCUR OR IF YOU HAVE QUESTIONS PLEASE CONTACT
THE INVERTER MARKETING DEPARTMENT AT 1-800-231-1412.