8.6.2
Ammeter (AM) Connection and Procedures
Terminal Connection (AM)
AM
Ammeter
Key
Adjustments should be made during a run. For this example the inverter
is running at 60Hz, and in the monitor mode.
2ND
Engages the "FM" calibration mode.
MON
NEXT
Engages the "AM" calibration mode.
RUN
Display indicates the output current values
Adjusts the current value of the analog meter. Press the "up"
or
or "down"
value.
WRT
Calibration of "AM" meter is complete
MON
Returns to actual frequency display
Notes:
The calibration procedure can be interrupted at any time by pressing the STOP key.
CC
+
-
Zero adjust
screw
Calibration Procedure (AM)
Action
key until the meter value equals the displayed inverter
8 - 20
Frequency Meter
(1mAdc ammeter or
7.5Vdc voltmeter)
Display
:
:
:
[value]
:
[value]
: