Starting/Stopping-Remote Control

The remote STARTING/STOPPING possibilities are identified in the following
figure and table.
Terminal Connection
ST-CC
F-CC
OFF
ON/OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON = short circuit
OFF = open circuit
Note:
1)
With ST-CC (ON), switching F-CC or R-CC (OFF) will cause the motor to decelerate to
a stop.
2)
If input power is turned off (with MCCB) while inverter is running, the motor will coast to
a stop.
3)
Acceleration and Deceleration rates are determined by the preset values of 1st
Function #2 (ACC/DEC).
4)
When switching from a forward run to a reverse run the motor will decelerate to a stop,
then accelerate in the reverse direction.
CAUTION
START/STOP Terminals Connections
ST
F
ST
F
Remote START/STOP Connections Possibilities
R-CC
ON/OFF
The inverter is OFF. OFF will be displayed. If running
when ST-CC is broken the motor will coast to a stop.
OFF
The inverter is ON but not running.
OFF
The inverter is ON and will run in a FORWARD direction if an
input signal is applied.
ON
The inverter is ON and will run in a REVERSE direction if an
input signal is applied.
ON
Same as REVERSE connection above.
Avoid using the input power switch (MCCB) to start and
stop the inverter. Use for an emergency stop only.