8.3.5
Function Function
No.
Name
Pattern run activation
mode
Time unit
Cycle times
2ND
8
Pattern drive time
#1 to 7
Pattern drive characteristics
#1 to 7
F/R, ACC/DEC
(Pt.1)
Pattern 1 acc.
(Pt.2)
Pattern 2 acc.
Forward run
Sr1
0
Reverse run
Pattern 1
(Pt.1t)

Pattern Run

The pattern run enables the user to run up to seven (7) different speeds
automatically, in either forward or reverse directions. It is an extension of the
7 Preset Speeds described in Section 8.3.4. Unlike the Preset Speed Function,
the user can pre-select the length of time in which the inverter will operate at
each frequency (Sr1-Sr7), as well as the acc/dec pattern used to reach each
frequency.
The required preset function parameters are as follows:
1)
Actual run frequencies (Sr1~Sr7) are located in 1st Function #6 (Section
8.3.4).
2)
The run time for each of these frequencies in the pattern (Pt.1t~Pt.7t) is
located in 2nd Function #8.
3)
The particular ACC/DEC drive characteristics to be used, as well as the
run direction (Pt.1~Pt.7) located in 2nd Function #8.
Function Parameters
Adjustment
Display
Range
0: Off
1: Terminal operation
2: Touch pad operation
3: Computer communication
0: Seconds
1: Minutes
0 to 255
(255: Infinity operating)
0 to 8000
to
0: Forward run, #1 ACC/DEC
1: Forward run, #2 ACC/DEC
to
2: Reverse run, #1 ACC/DEC
3: Reverse run, #2 ACC/DEC
The following graph shows a sample of a typical pattern run:
(Pt.3)
Sr2
Pattern 3 dec.
Pattern 3 acc.
Pattern 2
(Pt.2t)
Unit
sec
min
(Pt.4)
Pattern 4 dec.
(Pt.3)
Sr3
Pattern 3
Pattern 4
(Pt.3t)
(Pt.4t)
8 - 9
TOSHIBA
Factory
Error
Set
Message
0
0
0
0
0
(Pt.5)
Pattern 5 dec.
(Pt.5)
Pattern 5 acc.
Sr4
Sr5
Pattern 5
(Pt.5t)
Ref.
Page
8-28
8-28
8-28
8-28
8-28
Time