The power wiring terminals E1 through E3 for the 93PM 200 kW Three-Wire SIAC-B are pressure terminations.
Power wiring terminals E6 through E11 for the 93PM 200 kW Three-Wire SIAC-B are 2-hole bus bar mountings
for standard NEMA 2-hole barrel lugs. The power wiring connections for this equipment are UL and CSA rated.
See Table 3-8 for external power cable terminations, Table 3-10 for supplied external wiring terminal hardware,
and Table 3-11 for recommended installation parts and tools not supplied by Eaton.
Figure 4-19 or Figure 4-20 shows the location of the SIAC-B power cable terminals.

Table 3-8. External Input Power Cable Terminations for the Eaton 93PM 200 kW Three-Wire SIAC-B

Terminal Function
AC Input to RIB – Source 1
(4-breaker version only
)
AC Input to Maintenance Bypass – Source 2
AC Output to Critical Load
Building, Inter-Cabinet, and Load Ground
The power wiring terminals E1 through E3 for the 93PM 200 kW Four-Wire SIAC-B are pressure terminations.
Power wiring terminals E6 through E11 for the 93PM 200 kW Four-Wire SIAC-B are 2-hole bus bar mountings
for standard NEMA 2-hole barrel lugs. The power wiring connections for this equipment are UL and CSA rated.
See Table 3-9 for external power cable terminations, Table 3-10 for supplied external wiring terminal hardware,
and Table 3-11 for recommended installation parts and tools not supplied by Eaton.
Figure 4-19 or Figure 4-20 shows the location of the SIAC-B power cable terminals.

Table 3-9. External Input Power Cable Terminations for the Eaton 93PM 200 kW Four-Wire SIAC-B

Terminal Function
AC Input to RIB – Source 1
(4-breaker version only
)
AC Input to Maintenance Bypass – Source 2
AC Output to Critical Load
Building, Inter-Cabinet, and Load Ground
3-20
Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual
Number and Size of Pressure
Terminal
Function
E1 (RIB–1)
Phase A
E2 (RIB–3)
Phase B
E3 (RIB–5)
Phase C
E6
Phase A
E7
Phase B
E8
Phase C
E9
Phase A
E10
Phase B
E11
Phase C
TBG
Ground
Number and Size of Pressure
Terminal
Function
E1 (RIB–1)
Phase A
E2 (RIB–3)
Phase B
E3 (RIB–5)
Phase C
E6
Phase A
E7
Phase B
E8
Phase C
E12
Neutral
E9
Phase A
E10
Phase B
E11
Phase C
E12
Neutral
TBG
Ground
Termination
Tightening Torque
(AWG or kcmil)
Nm (lb ft)
2 – 3/0–250
2 – 3/0–250
2 – 3/0–250
2 – 2 bolt mounting
2 – 2 bolt mounting
2 – 2 bolt mounting
2 – 2 bolt mounting
2 – 2 bolt mounting
2 – 2 bolt mounting
4 – #14–1/0
5.1 Nm (45 lb in)
Termination
Tightening Torque
(AWG or kcmil)
Nm (lb ft)
2 – 3/0–250
2 – 3/0–250
2 – 3/0–250
2 – 2 bolt mounting
2 – 2 bolt mounting
2 – 2 bolt mounting
4 – 2 bolt mounting
2 – 2 bolt mounting
2 – 2 bolt mounting
2 – 2 bolt mounting
4– 2 bolt mounting
4 – #14–1/0
5.1 Nm (45 lb in)
P-164000387—Rev 7
Size Screw and Type
42 (31)
5/16" Hex
42 (31)
5/16" Hex
42 (31)
5/16" Hex
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
Slotted
Size Screw and Type
42 (31)
5/16" Hex
42 (31)
5/16" Hex
42 (31)
5/16" Hex
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
35 (26)
M12 Hex Bolt
Slotted