Page 4
Eaton is registered trademarks of Eaton or its subsidiaries and affiliates. National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies.
Page 7
3-24 Figure 4-1. Removing the Pallet Skids and Supports – Eaton 93PM Field Installed SIAC-B ..... . Figure 4-2. Cabinet Attaching Brackets ............. .
Page 8
Eaton 93PM 150 kW SIAC-B (Three or Four Wire) or Eaton 93PM 200 kW SIAC-B (Three or Four Wire) Breakers – Left-Mounted SIAC-B ....
Page 9
Table 3-11. Recommended Installation Parts and Tools (Not Supplied by Eaton) ......
Page 10
List of Tables This page intentionally left blank. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
2-hole bus bar lug input and output terminals reduce installation time. Power wiring between the UPS and SIAC-B are factory installed. Output power wiring to the critical load is routed using external conduit. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Model Configurations The following model configurations are available: Eaton 93PM 150 kW Three-Wire SIAC-B, Eaton 93PM 150 kW Four-Wire SIAC-B, Eaton 93PM 200 kW Three-Wire SIAC-B, and Eaton 93PM 200 kW Four-Wire SIAC-B - Right-mounted two breaker configuration containing a MBP with auxiliary contacts and MIS...
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Introduction For More Information Refer to the Eaton 93PM UPS (20–150 kW, 480V – 150 kW Capacity Frame) Installation and Operation Manual, the Eaton 93PM UPS (20–150 kW, 480V Four Wire – 150 kW Capacity Frame) Installation and Operation Manual, the Eaton 93PM Emergency Lighting UPS (20–40 kW, 480V Four Wire – UL 924) Installation and Operation Manual, the Eaton 93PM UPS (20–200 kW, 480V –...
Keep surroundings uncluttered, clean, and free from excess moisture. Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Page 18
Safety Warnings This page intentionally left blank. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Chapter 3 Installation Plan and Unpacking This chapter includes planning for the Eaton 93PM 150 kW and 200 kW Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B). NOTE The SIAC-B is attached to and directly integrated with the UPS cabinet at the factory or after field installation on sight.
862 (1900) 831 (1833) 8 at 104 (229) The clearances required around the SIAC-B are the same as the attached UPS. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
UPS with Left-Mounted SIAC-B Dimensions are in millimeters [inches] Figure 3-2. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with 93PM 150 kW SIAC-B (Three or Four Wire) Dimensions (Top and Bottom Views) Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE The 93PM 150 kW Capacity UPS (three or four wire) is shown with a left-mounted SIAC-B. An UPS with a right-mounted SIAC-B is the mirror image. Figure 3-3. Eaton 93PM 150 kW Capacity UPS (Three or Four Wire) with Left-Mounted 93PM 150 kW SIAC-B (Three or Four Wire) –...
Dimensions are in millimeters [inches] Figure 3-5. Eaton 93PM 200 kW UPS (Three or Four Wire) with 93PM 200 kW SIAC-B (Three or Four Wire) Dimensions (Top and Bottom Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE The 93PM 200 kW UPS is shown with a left-mounted SIAC-B. An UPS with a right-mounted SIAC-B is the mirror image. Figure 3-6. Eaton 93PM 200 kW UPS (Three or Four Wire) with Left-Mounted 93PM 200 kW SIAC-B (Three or Four Wire) – Center of Gravity Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE The 93PM 150 kW Capacity UPS is shown with a left-mounted SIAC-B. An UPS with a right-mounted SIAC-B is the mirror image. Dimensions are in millimeters [inches] Figure 3-7. Eaton 93PM 150 kW Capacity UPS Cabinet with SIAC-B Front and Rear Floor Mounting Bracket Mounting Dimensions...
NOTE The 93PM 200 kW UPS is shown with a left-mounted SIAC-B. An UPS with a right-mounted SIAC-B is the mirror image. Dimensions are in millimeters [inches] Figure 3-8. Eaton 93PM 200 kW UPS Cabinet with SIAC-B Front and Rear Floor Mounting Bracket Mounting Dimensions Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
The term line-up-and-match refers to accessory cabinets that are physically located adjacent to the UPS. The term standalone refers to accessory cabinets that are located separate from the UPS. 3-14 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Table 3-2 or Table 3-3. Wire sizes listed are for copper wiring only. Table 3-2. External Power Wiring Requirements for the Eaton 93PM 150 kW Three-Wire SIAC-B and 93PM 200 kW Three-Wire SIAC-B – Two and Three Breaker Maintenance Bypass...
Installation Plan and Unpacking Table 3-3. External Power Wiring Requirements for the Eaton 93PM 150 kW Three-Wire SIAC-B and 93PM 200 kW Three-Wire SIAC-B – Four Breaker Maintenance Bypass Units Rating 60 Hz Basic Unit Rating Input/Output Voltage Volts 480/480...
UPS Installation and Operation manual, listed in paragraph 1.7, for the appropriate conductor and upstream breaker size. Table 3-4. External Power Wiring Requirements for the Eaton 93PM 150 kW Four-Wire SIAC-B and 93PM 200 kW Four-Wire SIAC-B – Two and Three Breaker Maintenance Bypass...
UPS Installation and Operation manual, listed in paragraph 1.7, for the appropriate conductor and upstream breaker size. Table 3-5. External Power Wiring Requirements for the Eaton 93PM 150 kW Four-Wire SIAC-B and 93PM 200 kW Four-Wire SIAC-B – Four Breaker Maintenance Bypass...
Interface wiring can be installed using the inter-cabinet wiring access pass-through or by routing wiring through conduit between cabinets. Install the interface wiring in separate conduit from the power wiring. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Right-Mounted SIAC-B Figure 3-10. Eaton 93PM 200 kW SIAC-B (Three or Four Wire) attached to a 93PM 200 kW UPS (Three or Four Wire) as Shipped on Pallet Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
Installation Plan and Unpacking Figure 3-11. Eaton 93PM Field Installed SIAC-B as Shipped on Pallet 3-24 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Chapter 4 Installation This chapter includes installation instructions for the Eaton 93PM 150 kW AND 200 kW Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B). NOTE The SIAC-B is attached to and directly integrated with the UPS cabinet at the factory or after field installation on sight. This section must be used along with the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, during installation.
Floor Protectors (2 places front) (2 places rear) Figure 4-1. Removing the Pallet Skids and Supports – Eaton 93PM Field Installed SIAC-B Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Page 47
16. Recycle the bolts along with the shipping braces and support brackets in a responsible manner. 17 . Reinstall the SIAC-B front panel and secure with retained screw. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
12. If necessary after the installing the attaching straps, secure the SIAC-B in position by adjusting the leveling feet until the cabinet is level and locked in place. 13. Proceed to paragraph 4.4. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
SIAC-B through the bottom of the SIAC-B and UPS inter-cabinet wiring access pass-through to the UPS cabinet terminals. See Figure 4-3 or Figure 4-4 for SIAC-B terminal locations. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for the UPS pass-through and terminal locations.
Page 51
14. In the SIAC-B, locate the cable with the Red Anderson connector and connect to the Red Anderson connector mounted to the cabinet sidewall (see Figure 4-3 or Figure 4-4). 15. Proceed to paragraph 4.4.2 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for the UPS pass-through location. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Connect the MBP interface harness white two position connector to the UPS MBP interface terminal block connector (see Figure 4-13). Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, to complete the mechanical installation of the UPS and SIAC-B. After completing the mechanical installation return to paragraph 4.7.
Electrically Disconnecting the UPS Cabinet and SIAC-B To disconnect wiring: Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for UPS operating instructions.
If installing a four-wire SIAC-B, reconnect the tagged neutral wiring to the respective UPS terminals. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for terminal locations and requirements. 4-18 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Reconnect the UPS MBP interface harness connector to the UPS MBP interface terminal block connector (see Figure 4-11 or Figure 4-12, and Figure 4-13). Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, to complete the mechanical installation of the UPS and SIAC-B. After completing the mechanical installation return to paragraph 4.7.
Table 3-3 and Table 3-8 through Table 3-11 for SIAC-B wiring and termination requirements. For SIAC-B terminal phase wiring assignments, see Figure 4-19 or Figure 4-20. 4-20 Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Page 65
18. Reinstall the internal safety shield panel and secure with retained screws. 19. Reinstall the SIAC-B front panel and secure with retained screw. 20. After the SIAC-B is wired, return to the applicable Eaton 93PM UPS installation and operation manual, listed in paragraph 1.7, to complete the UPS wiring.
W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
NOTE Callout letters A and C map to Table 3-2. 200 kW Frame models contain a maximum of four UPMs. Figure 5-4. Eaton 93PM 150 kW or 200 kW Three-Wire UPS with Two-Breaker 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B System Online Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE Callout letters A and C map to Table 3-2. 200 kW Frame models contain a maximum of four UPMs. Figure 5-5. Eaton 93PM 150 kW or 200 kW Three-Wire UPS with Three-Breaker 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B System Online Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE Callout letters A, B, and C map to Table 3-3. 200 kW Frame models contain a maximum of four UPMs. Figure 5-6. Eaton 93PM 150 kW or 200 kW Three-Wire UPS with Four-Breaker 93PM 150 kW Three-Wire SIAC-B or 93PM 200 kW Three-Wire SIAC-B System Online Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE Callout letters A and C map to Table 3-4. 200 kW Frame models contain a maximum of four UPMs. Figure 5-7. Eaton 93PM 150 kW or 200 kW Four-Wire UPS with Two-Breaker 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B System Online Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE Callout letters A and C map to Table 3-4. 200 kW Frame models contain a maximum of four UPMs. Figure 5-8. Eaton 93PM 150 kW or 200 kW Four-Wire UPS with Three-Breaker 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B System Online Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
NOTE Callout letters A, B, and C map to Table 3-5. 200 kW Frame models contain a maximum of four UPMs. Figure 5-9. Eaton 93PM 150 kW or 200 kW Four-Wire UPS with Four-Breaker 93PM 150 kW Four-Wire SIAC-B or 93PM 200 kW Four-Wire SIAC-B System Online...
CLOSED RIB (if installed) CLOSED Start the UPS. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for UPS operating procedures. Reinstall the SIAC-B front panel and secure with retained screw. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7...
Retain screw for later use. Transfer the UPS from normal mode to bypass mode. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for UPS operating procedures.
Page 97
Retain screw for later use. If installed, close the BIB. If installed, close the RIB. Start the UPS in bypass mode. Refer to the applicable Eaton 93PM UPS Installation and Operation manual, listed in paragraph 1.7, for UPS operating procedures. CAUTION Failure to close the MIS before opening the MBP will result in the loss of power to the critical load.
Page 98
SIAC-B Operating Instructions This page intentionally left blank. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
Maintenance Training A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Customer Reliability Center (see paragraph 1.7).
Page 100
Maintenance This page intentionally left blank. Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (150 kW and 200 kW SIAC-B) Installation and Operation Manual P-164000387—Rev 7 www.eaton.com/powerquality...
For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton.
Page 104
Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.
Need help?
Do you have a question about the 93PM 150 kW SIAC-B Three-Wire and is the answer not in the manual?
Questions and answers