When the unit starts, i.e. on/off is pressed the Vent sequence is
initiated.
The venting sequence is divided into two phases. In the first
phase the cool output energize for the set venting sequence
time, VT1. This is followed by a second phase in which the
cool, and pump outputs are energized for the VT2 time.
To access the Vent Timer setups:
1
Press and hold the "enter" key till Uni is
shown on screen.
2
Press the "down" key till VT1 is shown on
screen.
3
Press the "enter" key to display the value.
(15 second default).
4
Press the "up/down" keys to change the
value.
5
Press the "enter"key to accept the change
in value.
Vent Bypass
If the unit remains full of fluid and it is not advantageous to
vent the unit may be bypassed on start-up.
1
Press and hold
begins immediately.
UGH025-0504
until the vent cycle
Thermolator TW Series
TW-1, TW-2
C
ONTROL
V
T
ENT
A
DJUSTMENT
M
AINTENANCE
IMER
5-15