Conair Thermolator TW-1 User Manual page 15

Water temperature control units
Table of Contents

Advertisement

MODEL DESIGNATIONS
T W
PERFORMANCE CHARACTERISTICS -
Models
Minimum Setpoint Temperature °F {°C}
Maximum Setpoint Temperature °F {°C}
Minimum Operating Temperature °F {°C}
Standard Cooling Valve Size inches {mm}
Available pump sizes
Available heater sizes
PUMP PERFORMANCE -
Consult your Conair representative for pump performance characteristics at other operating points.
Pump
Nominal Flow
gpm {lpm}
Pressure@ Nominal Flow psi {kg/cm
DIMENSIONS in. {mm}
Cabinet Style
Height
Depth
Width
SHIPPING WEIGHT RANGES lbs {kg}
Pump
0.75 HP {0.56 kW}
1 HP
{0.75 kW}
2 HP
{1.49 kW}
3 HP
{2.24 kW}
5 HP
{3.73 kW}
7.5 HP
{5.59 kW}
TOTAL FULL LOAD AMPS PER ZONE All voltages are 3 phase, 60 Hz.
Heater
9 kW
Voltage
208V 230V 460V 575V 208V 230V 460V 575V 208V 230V 460V 575V 208V 230V 460V 575V
Pump
0.75 HP {0.56 kW} 28.9 26.2 13.1 10.5 37.3 33.8 16.9 13.5 54.0 48.8 24.4 19.5 70.7 64.0 32 25.6
1 HP
{0.75 kW} 29.4 26.6 13.3 10.6 37.8 34.2 17.1 13.7 54.4 49.2 24.6 19.7 71.2 64.4 32.2 25.8
2 HP
{1.49 kW} 31.8 28.8 14.4 11.5 40.2 36.4 18.2 14.6 56.8 51.4 25.7 20.6 73.6 66.6 33.3 26.6
3 HP
{2.24 kW} 34.7 31.4 15.7 12.6 43.1 39.0 19.5 15.6 59.7 54.0 27.0 21.6 76.5 69.2 34.6 27.7
5 HP
{3.73 kW} 38.5 34.8 17.4 13.9 46.9 42.4 21.2 17.0 63.4 57.4 28.7 23 80.2 72.6 36.3 29.0
7.5 HP {5.59 kW} 45.7 41.4 20.7 16.6 54.1 49.0 24.5 19.6 70.7 64.0 32.0 25.6 87.5 79.2 39.6 31.7
TOTAL FULL LOAD AMPS PER ZONE All voltages are 3 phase, 60 Hz.
Heater
0 heaters
Voltage
208V 230V 460V 575V
Pump
0.75 HP {0.56 kW}
3.9 3.6 2.3
1 HP
{0.75 kW}
4.4 4.0 2.5
2 HP
{1.49 kW}
6.8 6.2 3.6
3 HP
{2.24 kW}
9.7 8.8 4.9
5 HP
{3.73 kW} 13.5 12.2 6.6
7.5 HP {5.59 kW} 20.7 18.8 9.9
UGH025-0504
Direct Injection (DI)
Closed Circuit (CC)
Isolated Circuit (IC)
*Lower operating temperatures can be obtained with larger cooling valves. Consult your Conair representative.
TW-DI
32 {0}
250 {121}
Approximately 20° {11°} above the cooling water inlet temperature*
1/4 {6.35}
0.75, 1, 2, 3, 5 or 7.5 Hp {0.56, 0.75, 1.49, 2.24, 3.73 or 5.59 kW}
9, 12, 18, 24, 36 or 48 kW
3/4 HP {0.56 kW}
1 HP {0.75 kW}
40 {151}
45 {170}
2
}
17 {1.2}
18 {1.3}
A
B
28.0 {710}
28.0 {710}
22.5 {570}
22.5 {570}
13.75 {350}
27.5 {700}
Weights vary depending on cabinet size and cooling type (DI, CC or IC).
Single Zone
Min
Max
240 {109}
300 {136}
240 {109}
300 {136}
250 {113}
310 {141}
260 {118}
320 {145}
270 {122}
330 {150}
280 {127}
340 {154}
12 kW
1.5
NOTE: Thermolators
1.6
can be ordered
without heaters for
2.5
certain applications.
3.6
4.9
7.6
Thermolator TW Series
S
TW-CC
32 {0}
250 {121}
3/4 {19.05}
2 HP {1.49 kW}
3 HP {2.24 kW}
55 {208}
80 {303}
31 {2.2}
35 {2.5}
C
43.0 {1090}
31.5 {800}
14.0 {355}
Dual Zone
Min
Max
480 {218}
600 {272}
480 {218}
600 {272}
500 {226}
620 {282}
520 {236}
640 {290}
540 {244}
660 {300}
560 {254}
680 {308}
18 kW
24 kW
PECIFICATIONS
TW-IC
32 {0}
180 {82}
3/4 {19.05}
9, 12, 18 or 24 kW
5 HP {3.73 kW}
7.5 HP {5.59 kW}
100 {379}
115 {435}
43 {3}
51 {3.6}
D
43.0 {1090}
31.5 {800}
28.0 {710}
36 kW
48 kW
208V 230V 460V 575V 208V 230V 460V 575V
104.0 94.0 47.0 37.6 137.0 124.0 62.1 49.7
104.3 94.4 47.2 37.8 137.7 124.6 62.3 49.6
106.7 96.6 48.3 38.6 140 126.8 63.4 50.7
109.6 99.2 49.6 39.7 143 129.4 64.7 51.8
113.4 102.6 51.3 41.0 146.7 132.8 66.4 53.1
120.7 109.2 54.6 43.7 154 139.4 69.7 55.8
D
ESCRIPTION
2-7