TARTING THE
TW
If, after setting the set-
point to the desired tem-
perature, the optional
Fault light/ alarm
turns on, press the
FAULT button to
silence the alarm.
Then go to
the Troubleshooting sec-
tion to correct problem.
4-6
O
PERATION
Before starting the Thermolator, verify that the system has
been installed correctly for your application. See Installation,
section 3.
1
Turn on the water supply to the Thermolator.
The supply pressure must be at least 25 psi. Check for
leaks in the cooling water and process fluid lines before
continuing.
2
Turn on main power to the Thermolator.
3
Set the temperature setpoint to 100° F.
Press
to increase or
ture setting. Press
4
Press and hold START
cycle begins.
If everything is working correctly:
u The Cooling indicator lights.
u The unit initiates a variable venting sequence. The
pump starts after the vent time 1 is over.
u Normal operation begins. The heater turns on if the
actual temperature is below setpoint. The cooling valve
is active if the actual temperature is above setpoint.
5
Set the setpoint to the desired temperature.
Press
to increase or
ture setting. Press
Thermolator TW Series
to decrease the tempera-
to accept.
until the vent
to decrease the tempera
to accept.
UGH025-0504