Conair Thermolator TW-1 User Manual page 63

Water temperature control units
Table of Contents

Advertisement

6
Press the up s key to begin calibrating.
The controller displays the name of the current calibration
(examples: 32 SC.L; 32 rC.L; 510 SC.H; or 510 rC.H).
7
Wait until the control displays 'don' or 'bad'.
A "don" message in the Setpoint display indicates the cal-
ibration was successful. A "bad" message in the Setpoint
display indicates a bad calibration.
NOTE: The original calibration value stored in
EEProm can be restored for the current calibration
by pressing the STOP key at any time.
8
Press Select
Pressing and releasing the Select
calibration tells the controller to perform the next calibra-
tion.
9
Exit Calibration Mode.
Press and hold the Select
Calibration Mode.
You can now proceed to the next test in Test Mode, or disable
Test Mode and resume normal operation.
TO DISABLE TEST MODE, complete steps 2
through 5 in "Performing System Tests", setting dip
switch 6 to OFF instead of ON.
UGH025-0504
to start the next calibration.
key at the end of a
key for 3 seconds to exit the
Thermolator TW Series
TW-1, TW-2
C
ONTROL
C
ALIBRATING
T
EMPERATURE
S
ENSORS
5-11
M
AINTENANCE