The Output Test verifies the function of outputs available on
the models with TW-1 or TW-2 controls. Not all outputs are
used on all models. The performance evaluation of the inputs
is based on the output monitors (OM).
1
Connect all outputs to the system.
IMPORTANT: Testing each output requires the fir-
ing of the associated solid state relay. Make sure
an output device is connected to the controller, oth-
erwise the test result will be erroneous.
2
Enable Test Mode.
3
Press any key to display the first test menus.
4
Select the Output Test menu.
Press and hold the Setpoint
index to each test menu until the controller displays
"oUt".
5
Repeatedly press and release any key to test.
With each key press and release, the left display will indi-
cate the number of the output being tested (oS1= OM1;
oS2 = OM2; etc.). The right display indicates either "1"
for a good output or "O" for a failed output.
Only outputs that are actually used by the particular
model will be tested.
6
Exit the test and enter the next test.
Press and hold the Setpoint
and index to the next test.
Thermolator TW Series
key for 3 seconds to
key for 3 seconds to exit
UGH025-0504