Fluid Levels - Conair Thermolator TW-1 User Manual

Water temperature control units
Table of Contents

Advertisement

C
HECKING THE
R
ESERVOIR
F
L
LUID
EVEL
(IC
)
MODELS ONLY
5-4
M
AINTENANCE
The isolated, or totally closed circuit models separate the cool-
ing water from the process fluid, which is held in a reservoir
inside the unit. This reservoir should be kept at about three-
quarters full of the process fluid.
You can check the fluid level
in the reservoir using the sight
glass on the back of the
Thermolator.
To fill the reservoir:
1
Disconnect and lockout power, and remove the
top panel of the Thermolator.
2
Locate the reservoir near the top of the unit.
3
Locate the fill port at the top of the reservoir.
4
Refill the reservoir. Monitor the level using the
sight glass on the back of the unit. Because IC units can
use pure water or glycol mixtures, make sure you are
adding the correct fluid for your application.
IMPORTANT: Do not use deionized water or gly-
col mixtures containing additives in a Thermolator.
Softened water or glycol mixtures with additives,
such as automotive fluids, can damage the
Thermolator. Glycol/water process loop mixtures
should use industrial-grade ethylene glycol only.
5
Replace the top panel of the Thermolator.
Thermolator TW Series
Sight glass
UGH025-0504