Conair Thermolator TW-1 User Manual page 107

Water temperature control units
Table of Contents

Advertisement

The Thermolator will not operate correctly if certain factory-set
parameters are changed. Parameters should be changed only by
qualified technical personnel who are familiar with the operation of
this type of equipment.
If the Thermolator does not appear to be working correctly, verify
the parameters against the list of factory settings.
For more detailed information about these parameters and return-
ing parameters to the initial factory setup, See the Series 16C
Instruction Manual included with this instruction package.
Menu
Function
SET
ASP
Active Setpoint
Uni
Unit of Measure
PUr
Process Variable
Pit
Proportional Integral Tuning
dSP
Deviation from Setpoint
ddt
Deviation Alarm Delay Time Period
Ut1
Vent Time Period 1
Ut2
Vent Time Period 2
AAt
Alarm Acknowledge Timer
t01
Thermolator Version Release 01
SLo
Slow Proportional Prop Band
nor
Normal Proportional Prop Band
FSt
Fast Proportional Prop Band
db
Dead Band
CCt
Cooling Cycle Time
Ci
Cooling Integral Time Period
HCt
Heating Cycle Time
Hi
Heating Integral Time Period
PrS
Power-Up Restart Selector
rSS
Remote Setpoint Selector
PiC
Proportional to Integral
Crossover Percent
UGH025-0504
User Level (1 sec)
Setpoint
Configuration Level (5 sec)
Service Level (15 sec)
Range
20-250ºF (-6.6-121.5ºC)
Read Only
ºF or ºC
to = To Temperature
Fro = From Temperature
AUG = Average Temperature
rE = Remote Temperature
SL0 = Slow
nor = Normal
FSt = Fast
0-45ºF (0-25ºC)
0-600 seconds
0-999 seconds
0-999 seconds
0-60 minutes
Read Only
0.2-180°F (0.1-100°C)
0.2-180°F (0.1-100°C)
0.2-180°F (0.1-100°C)
0-10°F (0-5.6°C)
0-60 seconds
0-999 seconds
0-60 seconds
0-999 seconds
on = Manual
oFF = Auto
oFF = Controller Setpoint Active
on = Remote Setpoint Active
0-100%
Thermolator TW Series
TW C
ONTROL
D
EFAULT
P
ARAMETERS
Default
75ºF
ºF
ºF
AUG
nor
20ºF
600 seconds
15 seconds
15 seconds
1 minute
t01
5°F
10°F
15°F
0.5°F
7 seconds
15 seconds
7 seconds
15 seconds
on
OFF
35%
A