Terminal X2 - KEB COMBIVERT F4-F Instruction Manual

Control circuit
Hide thumbs Also See for COMBIVERT F4-F:
Table of Contents

Advertisement

2.2. Terminal X2

PNP-Logic
1
2
3
4
ST
RST
F
R
Terminal
Name
Function
1
ST
Control release
2
RST
Reset
Software limit switch forward / *1
3
F
forward direction of rotation
Software limit switch forward / *1
4
R
reverse direction of rotation
Input for jogging speed forward
5
I1
see also parameter CP.11
Input for jogging speed reverse
6
I2
see also parameter CP.11
Input for external fault stopping mode
7
I3
see also parameter CP.15
digital output signal 1
8
D1
see also p
digital output signal 2
9
D2
see also p
10
Uout
+ 18 V Voltage output
11
0 V
Mass for Uout und digital I/Os
23
Ext. Volt. External power supply of control card
Digital In- / Outputs
5
6
7
8
I1
I2
I3
D1
arameter CP.21
arameter CP.22
2. Connection
internal
voltage supply
9
10
11
........
D2
U
0 V
Ext.
out
Volt.
Isolation between terminals for digital
signals (X2.1 - X2.11, X2.23) and terminals
for analog signals (X2.12 - X2.19).
Digital Inputs
Noise immunity: 2 kV
logic 1: ± 12...30 V
Interal input resistor: approx. 2,7 kΩ
PNP-Logic
* The function must be activated with CP.35.
If the unit is defective there is no guarantee
that the software protective function will work.
programmable PNP - transistor outputs
14...30V / max. 20 mA (per Output)
Voltage supply supplied from the inverter for digital
inputs and outputs
U
: 14...30V (depending on power circuit and load)
out
I
: max. 60 mA
out
+ 24 (+/- 25%) external voltage input
Ground: 0V (terminal X2.11)
(dependent on power circuit /
refer to Instruction Manual Part 2)
ANTRIEBSTECHNIK
The earth-fault terminal is
found in the power circuit!
(see instruction manual
part 2).