Basic Programming; Commissioning With Smartstart; Commissioning Via [Main Menu] - Danfoss VLT Aqua Drive FC 202 Operating Manual

0.25-30kw
Hide thumbs Also See for VLT Aqua Drive FC 202:
Table of Contents

Advertisement

Commissioning
Recommended initialization procedure via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to parameter 14-22 Operation Mode and
press [OK].
3.
Scroll to [2] initialization and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
The start-up may take slightly longer than normal.
6.
Alarm 80, Drive initialized to default value is shown.
7.
Press [Reset] to return to operating mode.
Manual initialization procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. The start-up may take slightly longer than usual.
Manual initialization does not reset the following
frequency converter information:
Parameter 15-00 Operating hours.
Parameter 15-03 Power Up's.
Parameter 15-04 Over Temp's.
Parameter 15-05 Over Volt's.

5.4 Basic Programming

5.4.1 Commissioning with SmartStart

The SmartStart wizard enables fast configuration of basic
motor and application parameters.
SmartStart starts automatically at first power-up
or after initialization of the frequency converter.
Follow the on-screen instructions to complete the
commissioning of the frequency converter.
Always reactivate SmartStart by selecting Quick
Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to chapter 5.4.2 Commissioning via
[Main Menu] or the programming guide.
NOTICE
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
MG20MD02
Operating Guide
The SmartStart configures the frequency converter in 3
phases, each consisting of several steps, see Table 5.6.
1
Basic Programming
2
Application Section
3
Water and Pump Features
Table 5.6 SmartStart, Setup in 3 Phases

5.4.2 Commissioning via [Main Menu]

Recommended parameter settings are intended for start-
up and check-out purposes. Application settings may vary.
Enter data with power ON, but before operating the
frequency converter.
1.
2.
Illustration 5.2 Main Menu
3.
Illustration 5.3 Operation/Display
Danfoss A/S © 10/2016 All rights reserved.
Phase
Perform the programming
Select and program
appropriate application:
Single pump/motor.
Motor alternation.
Basic cascade control.
Master/slave.
Go to water and pump
dedicated parameters.
Press [Main Menu] on the LCP.
Press the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
1107 RPM
3.84 A
Main menu
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
Press the navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
0.0%
0.00A
Operation / Display
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
LCP Custom Readout
*
Action
5
5
1 (1)
1(1)
0-
**
27

Advertisement

Table of Contents
loading

Table of Contents