Danfoss VLT Aqua Drive FC 202 Operating Manual page 19

0.25-30kw
Hide thumbs Also See for VLT Aqua Drive FC 202:
Table of Contents

Advertisement

Electrical Installation
1
9
10
L1
L2
L3
PE
1
PLC
2
Frequency converter
3
Output contactor
4
Grounding rail (PE)
5
Cable insulation (stripped)
Illustration 4.3 EMC-compliant Connection of Mains
NOTICE
EMC INTERFERENCE
Use shielded cables for motor and control wiring and separate cables for input power, motor wiring, and control wiring.
Failure to isolate power, motor, and control cables can result in unintended behavior or reduced performance. Minimum
clearance requirement between power, motor, and control cables is 200 mm (7.9 in).
MG20MD02
Operating Guide
2
11
8
6
6
Cable gland
7
Motor, 3-phase, and PE
8
Mains, 3-phase, and reinforced PE
9
Control wiring
10
Equalizing minimum 16 mm
Danfoss A/S © 10/2016 All rights reserved.
3
4
5
u
v
w
PE
7
2
(5 AWG)
4
4
17

Advertisement

Table of Contents
loading

Table of Contents