Danfoss VLT Aqua Drive FC 202 Operating Manual page 22

0.25-30kw
Hide thumbs Also See for VLT Aqua Drive FC 202:
Table of Contents

Advertisement

Electrical Installation
4
4
Illustration 4.9 Terminal Numbers
Connector 1 provides:
-
-
-
-
Connector 2 terminals (+)68 and (-)69 are for an
RS485 serial communication connection.
Connector 3 provides:
-
-
-
-
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software.
Terminal
Parameter
12, 13
20
VLT
1
12 13 18 19 27 29 32 33 20 37
2
3
61
68
69
39
42 50 53 54 55
4 programmable digital inputs terminals.
2 extra digital terminals programmable
as either input or output.
24 V DC terminal supply voltage.
Optional customer supplied 24 V DC
voltage.
2 analog inputs.
1 analog output.
10 V DC supply voltage.
Commons for the inputs and output.
Terminal description
Default
setting
Description
Digital Inputs/Outputs
+24 V DC
24 V DC supply voltage
for digital inputs and
external transducers.
Maximum output
current 200 mA for all
24 V loads.
Danfoss A/S © 10/2016 All rights reserved.
®
AQUA Drive FC 202
Terminal
18
19
32
33
27
29
20
37
39
42
50
53
54
55
Terminal description
Default
Parameter
setting
Parameter 5
-10 Termina
l 18 Digital
Input
[8] Start
Parameter 5
-11 Termina
l 19 Digital
[0] No
Input
operation
Digital inputs.
Parameter 5
-14 Termina
l 32 Digital
[0] No
Input
operation
Parameter 5
-15 Termina
l 33 Digital
[0] No
Input
operation
Parameter 5
-12 Termina
l 27 Digital
[2] Coast
For digital input or
Input
inverse
output. Default setting
Parameter 5
[14] Jog
is input.
-13 Termina
l 29 Digital
Input
Common for digital
inputs and 0 V
potential for 24 V
supply.
Safe Torque
Safe input (optional).
Off (STO)
Used for STO.
Analog Inputs/Outputs
Common for analog
output
Parameter 6
Speed 0 –
Programmable analog
-50 Termina
High Limit
output. 0–20 mA or 4–
l 42 Output
20 mA at a maximum
of 500 Ω
+10 V DC
10 V DC analog supply
voltage for potenti-
ometer or thermistor.
15 mA maximum
Parameter
group 6-1*
Analog
Input 53
Reference
Parameter
Feedback
Analog input. For
group 6-2*
voltage or current.
Analog
Switches A53 and A54
Input 54
select mA or V.
Common for analog
input
Serial Communication
Description
MG20MD02

Advertisement

Table of Contents
loading